- The device must be supplied with 230V, 50Hz.
- Mains connection must be ensured using the 3-wire cable factory
fitte to the heater , through a connecting box. In damp premises, such
as bathrooms and kitchens, install the connecting box at least 25cm
from the ground.
- The installation must comply with local national regulation. If in
doubt, ask the national Atlantic distributor.
- Ground connection is forbidden.
do not connect the pilot wire (black) to ground.
- If power cable is damaged or too short, to avoid any danger it must
be replaced by a qualified electrician using special tools.
- If a heater pilots or is piloted by a 30mA differential (e.g. bathroom),
the pilot wire supply must be protected on this differential.
3) Programming
The device can be controlled remotely if its pilot wire is connected to
a device fitted with a programmer, a programming unit or an energy
management unit.
This device must be installed with a remotely controllable
programming system.This type of system can be connected
via the pilot wire of the device.
Chart indicating the orders the device can receive over its
(to be measured between the pilot wire and the neutral).
Orders received Current absent
Ref/neutral
oscilloscope
Mode achieved
Heating
temperature
pilot wire
Full alternance
230V
CONFORT
ECO
3°C to 4°C
CONFORT
below
setting
CONFORT
setting
Negative half-
alternance
-115V
STANDBY
Standby
temperature,
about 7°C
18
Positive half-
alternance +115V
STOP LOAD
SHEDDING
Stopping the hea-
ting immediately.
Can also be used
for load shedding.