FRONTAL PANEL DESCRIPTION

GENERAL FUNCTIONS OF THE PUMP :
- 4 LANGUAGES MENU: ITALIAN, ENGLISH, FRENCH, SPANISH
- pH or mV (Rx) CONTROL CHOICE
- 3 POSSIBLE TYPES OF FUNCTIONING: MANUAL, ON/OFF, PROPORTIONAL
- ALARM TIME OF OVERDOSAGE
- START UP DELAY
- DEFAULT PARAMETER RESTORING
- WATER FLOW CONTROL
- LEVEL CONTROL
- OVER RANGE AND UNDER RANGE OF THE MEASURE
- STOP DOSING ( STAND_BY )
- REAL TIME FLOW RATE %
type pH:
 FUNCTIONING: Prop
 SETPOINT: 7.2 pH
 DIRECTION DOSING: Acid
 Delay On: 0sec
 FLOW RATE:100%(maximum)
 ALARM TIME: 0unit (disabled)
 START UP DELAY: 3 sec
DEFAULT SETTINGS RESTORE
PUMP'S CONNECTIONS
Rev 1.0
DEFAULT SETTINGS
Push and quickly release CAL button and then pressing + and – buttons select "Restore
Enter"
Push CAL to confirm the choice. The pump goes back in pH measure restoring in memory
the default settings and calibrations parameters.
A – Power cable, 230 V- 50Hz (upon request : 115 ~ )
B – Level probe connector (3 and 4 contacts). OPTIONAL
C – Flow sensor connector (3 and 4 contacts). OPTIONAL
D - BNC connector for pH or Orp(Rx) probe.
E - ON_OFF switch. OPTIONAL
Cod. 00.008.646
1.Display LCD 8 x 2 backlight
2.Green Led: ▪ fix = PUMP ON
▪ blinking = PUMP IN ALARM
3.Red Led: continuously lit on indicates the dosing
4.CAL button : ▪ allows to enter in programming
▪ saves the changes
5/6. – and + buttons : ▪ allows to navigate through the
7. ESC/SBY button: ▪ puts the pump in stand_by mode
type Rx:
 FUNCTIONING: Prop
 SETPOINT: 730mV
 DIRECTION DOSING: Oxid
 Delay On : 0sec
 FLOW RATE: 100% (maximum)
 ALARM TIME: 0unit (disabilitato)
 START UP DELAY: 3 sec
menu
▪ Modify the parameters values
▪ allows to exit the menu
11