Installation
Piping Diagrams
Single Valve Installation at or near Hot Water Source
high temperature hot (if required for laundry, etc.)
tempered water main hot supply to system
valve
hot
water
thermometer
tank,
heater,
etc.
Diagram 1 INSTALLATION AT OR NEAR THE HOT
WATER SOURCE: TempControl must be positioned
below the hot water tank or heater, well below the high
temperature water line. This procedure creates a heat
trap and protects against hot water migrating through
the controller.
Single Valve Installation with Recirculating
Tempered Water at Hot Water Source
high temperature hot (if required for laundry, etc.)
tempered water main hot supply to system
valve
hot
thermometer
water
tank,
heater,
etc.
check
ball valve
Diagram 2 INSTALLATION WITH RECIRCULATING
TEMPERED WATER AT HOT WATER SOURCE: Temp-
Control must have the return line connected exactly as
shown. This procedure allows the controller to maintain
the set temperature during periods of no draw by (a)
allowing the major volume of return water to supply the
cold inlet of the TempControl and (b) the minor volume
of return water to be reheated and supply the hot inlet
of the TempControl. When there is no water draw on the
plumbing system, no water can be added to the system;
therefore, the "cold" and "hot" supplies to the Temp-
Control must come from within the system as described
below using the ball valve for fine tuning the operation
as outlined in (a) and (b).
Diagram 1
TempControl thermostatic
water controller
valve
cold supply
Diagram 2
TempControl thermostatic
water controller
circulating pump
check
thermometer
tempered water return
valve
cold supply
Remote HI-LOW System Installation with
Recirculating Tempered Water
PRV valve
thermometer
P1 pressure gauge
V1 valve
TMV1
hot supply
cold supply
tempered water return to cold inlet of heater
Diagram 3 REMOTE HI-LOW INSTALLATION WITH
RECIRCULATING TEMPERED WATER OR HOT WATER
RETURN: TempControl Hi-Low system must have the
return line connected exactly as shown (See Diagram 2
notes).
Remote HI-LOW System Installation with
thermometer
PRV valve
P1 pressure gauge
V1 valve
TMV1
hot supply
hot water return
cold supply
Diagram 4 REMOTE HI-LOW INSTALLATION WITH
RECIRCULATING HOT WATER SUPPLY ONLY:
TempControl Hi-Low system must be piped as shown.
9
Diagram 3
tempered water to showers, lavatories, etc.
P2 pressure gauge
V2 valve
TMV2
circulating pump
check
check
ball valve
Diagram 4
Recirculating Hot Water
tempered water to showers,
lavatories, etc.
P2 pressure gauge
V2 valve
TMV2
thermometer