DIAGRAM FOR TESTING THE WRGA-02/D WITHOUT GENERATOR
Below is the connection diagram for bench testing the regulator to verify proper operation of the equipment.
NOTES
1.
The setup for single phase sensing voltage should be made.
220V/100W lamp or resistor for rated current.
ATTENTION
1.
The lamp voltage must be the same voltage applied on the input. The figure 24.1 shows an
example using a 220V/100W lamp.
Voltage variation 90 to 120Vac.
Input
110Vac
Figure 24.1 - Regulator connection without generator.