Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7
TEST RUN
• See the installation manual accompanying indoor unit.
• Be sure to perform test run of indoor unit individually, and
then to perform all the units simultaneously.
• After the unit is turned off, the unit will not start operation for
3 minutes to protect the unit.
8

ITEMS TO CHECK

Is the specifi ed power supply voltage used?
Is the connecting cable fi xed to terminal board fi rmly?
Is the earth wire connected properly arranged?
Is the drainage properly?
Is there any gas leakage at the pipe connection?
5°F(-15°C) AUTO STOP FUNCTION
• During the heating operation, the unit will automatically stop when
the outdoor temperature drops below 5°F(-15°C) to prevent the
outdoor unit from the damage caused by the freezing of the drained
water. The unit will stop its operation for 4 hour and then resume the
operation when the outdoor temperature rises above 7°F(-13.9°C).
• To inactivate this function, slide the SELECT switch(DSW1) #1 to
OFF side.
Note:
• Make sure not to slide the SELECT switch(DSW1) #2 to OFF side.
PUMP DOWN
Pump down is adopted in the case of unit removal for re-installation, abandonment, repair etc.
Pump down is to collect the refrigerant into the outdoor unit.
PROCEDURE USING GAUGE MANIFOLD (Recommended procedure)
(
1) Connect the gauge manifold hose to the service port of the stop valve(gas side).
(2) To start pump down, press the PUMP DOWN button(SW1) for 5 seconds or more.
The OPERATION lamp on the indoor unit will fl ash and three BEEP will be emitted.
(3) After 5-10 minutes, fully close the stop valve (liquid side).
(4) Close the stop valve (gas side) when the compound gauge reading becomes almost
0 MPa(0 cmHg).
(5) To stop the pump down, press the PUMP DOWN button(SW1) for 5 seconds or more.
(6) Disconnect the gauge manifold hose from the service port.
PROCEDURE WITHOUT USING GAUGE MANIFOLD
(1) To start pump down, press the PUMP DOWN button(SW1) for 5 seconds or more.
The OPERATION lamp on the indoor unit will fl ash and three BEEP will be
emitted.
(2) After 5-10 minutes, fully close the stop valve (liquid side) .
(3) After 2-3 minutes, close the stop valve (gas side) fully.
(4) To stop the pump down, press the PUMP DOWN button(SW1) for 5
seconds or more.
Caution:
• Make sure that the compressor is turned off before removing the refrigerant
pipes. Otherwise, it will cause burst and injury.
• Do not perform PUMP DOWN when refrigerant is leaking or there is no refrigerant in
the refrigerant cycle. Otherwise, it will cause burst and injury.
• In order to prevent malfunctioning of compressor, be sure to turn off the pump down
operation within 20 minutes after closing the stop valve of liquid side.
Note:
• Wait more than 90 seconds after fi nishing pump down, and turn off the
circuit breaker off.
IM_A3AEX4M3PU(B434)_EN+FR+ES.indb EN-5
IM_A3AEX4M3PU(B434)_EN+FR+ES.indb EN-5
DSW1
1
2
OFF
ON
EXPLANATION TO CUSTOMER
• Explain to the customer how to use and maintain the system, referring to the
operation manual.
• Ask the customer to carefully read the operation manual.
• When the system has been set up, hand the installation manual to the
customer.
Service port
Stop valve
(gas side)
EN-5
SELECT switch (DSW1)
SELECT
DSW1
LED1A
1
2
OFF
ON
LED1B
PUMP DOWN
SW1
LED1C
LED1D
WIRE CHECK
SW2
Gauge manifold
Stop valve
(liquid side)
Compound
Lo
Hi
gauge
PUMP DOWN button (SW1)
SELECT
DSW1
LED1A
1
2
OFF
ON
LED1B
PUMP DOWN
SW1
LED1C
WIRE CHECK
LED1D
SW2
2/7/13 11:05:31 AM
2/7/13 11:05:31 AM

Publicidad

Tabla de contenido
loading

Tabla de contenido