2. Safety
WARNING!
Do not exceed the specifications for model T32.xS given in the data sheet
and operating instructions. In order to ensure a safe functionality of the current
output, the correct terminal voltage must be present in the instrument.
The following terminal voltage limits apply:
Instrument model
T32.1S.000-S
T32.3S.000-S
T32.1S.0IS-S
T32.3S.0IS-S
T32.1S.0NI-S
T32.3S.0NI-S
T32.1S.0IC-S
T32.3S.0IC-S
WARNING!
Only the temperature sensors listed in chapter 2.1 are approved for use in a
safety-related application.
The following sensors and operating modes are NOT allowed for operation in a
safety-relevant application:
Potentiometers
■
Other resistance sensors
■
Other mV sensors
■
Differential mode in duplex sensor operation
■
WIKA safety manual temperature transmitter T32.xS
Terminal voltage limits
DC 10.5 ... 42 V
DC 10.5 ... 30 V
DC 10.5 ... 40 V
DC 10.5 ... 30 V
EN