Electrical Connections
Two separate 120 VAC, 15 AMP circuits, which must be protected by a Ground Fault Circuit Interrupter (GFCI), are required. Install duplex
outlets to the studwall underneath the bathtub, at least 4 inches above the floor. The duplex outlets are not provided. One circuit is for the
pump/motor and the other is for the RapidHeat
Install a separate 120 VAC, 15 AMP dedicated circuit with GFCI protection. With a #8 solid copper wire, bond the heater to the house
electrical panel or approved local bond. A bonding lug is provided on the heater.
At initial start-up and before each use thereafter with power ON, push the GFCI test button. The reset button should pop out. Push this
button in to reset. If the interrupter fails to operate in this manner, there is a ground current flowing or a device malfunction, indicating the
possibility of electrical shock. Turn off power and do not use the bath until the source of the problem has been identified and corrected.
DANGER: RISK OF ELECTRIC SHOCK. Connect only to a circuit protected by a Ground Fault Circuit Interrupter.
CAUTION: Operating the motor/pump without enough water in the bath can cause leaking and permanent damage to the pump and/
or heater. Before power is applied to the installation, make sure the switch is in the OFF position to avoid pump damage.
ELECTRICAL CONNECTION WITH RAPIDHEAT
INSTALL SEPARATE
GFCI PROTECTED CIRCUITS
TM
HEATER
TM
heater.
ELECTRICAL CONNECTION
DUPLEX
RECEPT.*
4" MIN.
OR IN
ACCORDANCE
WITH LOCAL
BUILDING OR
ELECTRICAL
CODES
*(NOT PROVIDED)
7
(FOR CORNER BATHS)
TO HEATER
Jacuzzi Whirlpool Bath
EACH HAS 3
PRONG PLUG
DUPLEX
RECEPT.*
4" MIN.
OR IN
ACCORDANCE
WITH LOCAL
BUILDING OR
ELECTRICAL
CODES
FLOOR
*(NOT PROVIDED)
©
BP43000 2/05