Key Automation CT-24M Manual De Instrucciones página 36

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

GB
PROGRAMMING WORK AND SELF-LEARNING PAUSES
1. Bring the automation gate to approximately half its stroke.
2. Press the PROG button and keep it pressed for 3 seconds. The blinker or LED L1 will go on and remain on
steady warning that you have entered the programming procedure.
3. Press the P/P button to close the Gate all the way to the end of its stroke. After 2 second it will invert direction to
opening and the gate will be opened all the way (the entire learning procedure is performed in slow motion).
In case limit switches are not detected by the control unit, we advise users to turn both magnets by 180° on the
horizontal metal brackets on which magnets are fixed.
4. The
first maneuver
whether the motor is turning in the proper direction. If not, and the unit does not close. In this case run a
RESET by touching the two Pins marked RESET with the tip of a screwdriver. The control unit will immediately
block the operation, thus enabling you to invert polarity of the motor cables. Then repeat programming starting
from point 2.
5. The gate opens all the way to the limit switch.
6. Start the timing count for automatic closing and let the desired time elapse.
7. Press the P/P button once more or press the remote control button.
8. The gate starts the closing maneuver and continues until it has reached the fully closed limit switch.
9. The control unit automatically exits the programming procedure and Led LD1 goes off.
You can pre-calibrate or check the magnetic limit switches during programming.
PROCEDURE:
- Release the gate by triggering the motor, the gate will move freely.
- Enter programming mode by pressing the PROG button and keeping it pressed for 5 seconds.
- Manually move the gate. When it nears the limit switch the blinker and led DL1 will flash.
- Make the necessary adjustments.
- Lock the motor once more and proceed with point 3 of the self-learning procedure.
To ensure that the gate stops precisely when the limit switch is detected, we suggest activating
maximum slowdown (Dip 5 = ON) and minimum slowdown (Dip 1 = ON).
36
performed by the control unit is
closing
. This makes it possible for the unit to determine

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cabat-30

Tabla de contenido