5. TECHNICAL SPECIFICATIONS

5.1 CONNECTION AND INDICATIONS

CC11 Control
* It is possible to insert the accessory on slots 1 and 2 on the PLC300. The digital inputs and outputs are represented by DI10X/DO10X
(Slot 1) and DI20X/DO20X (Slot 2).
Figure 4: IOC-01– XC15 Terminal strip - Digital inputs as active high
XC15
PLC300(*)
1
DI9
DI101/DI201
2
DI10
DI102/DI202
3
DI11
DI103/DI203
4
DI12
DI104/DI204
5
DI13
DI105/DI205
6
DI14
DI106/DI206
7
DI15
DI107/DI207
8
DI16
DI108/DI208
9
COM
COM
10
NA6
NA101/NA201
11
C6
C101/C201
12
NA7
NA102/NA202
13
C7
C102/C202
14
NA8
NA103/NA203
15
C8
C103/C203
16
NA9
NA104/NA204
17
C9
C104/C204
18
NC
NC
Installation, Configuration and operation guide
Function
Digital Input 9
Digital Input 10
Digital Input 11
Digital Input 12
Digital Input 13
Digital Input 14
Digital Input 15
Digital Input 16
Common point of the
digital inputs
Digital Output 6 DO6 (RL6)
Digital Output 7 DO7 (RL7)
Digital Output 8 DO8 (RL8)
Digital Output 9 DO9 (RL9)
Specifications
8 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @
24 Vdc
Contact rating:
Maximum voltage: 240 Vac
Maximum current:1 A
NO - Normally open
contact
C - Common