Descargar Imprimir esta página

Festo CPV-GE-ASI-8E6A-Z Serie Manual De Instrucciones página 26

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
Type CPV...−GE−ASI−8E6A−Z M8
AS−Interface bus connection
Voltage range (protected against incorrect
polarity)
Residual ripple
Max. current consumption
all inputs 0−status
all inputs 1−status, no current
consumption by sensors (e.g. switches)
all inputs in 1−status, max. current
consumption by sensors
Load voltage connection
Rated value (protected against incorrect
polarity)
Residual ripple
Current consumption for 8 valves
when switched on (26.4 V)
when switched on (20.4 V)
after current reduction (stationary; 26.4 V)
after current reduction (stationary; 20.4 V)
Valves (see Pneumatics manual)
Digital inputs
Design
Logic level
Reference potential
Response delay
1)
e.g. per input 30 mA, incl. 7 mA for input circuit
2
) for max. 30 ms all valve coils switched simultaneously
26
1)
2
)
2
)
Festo CPV..−GE−ASI−8E6A−Z 0802a English
26.5 ... 31.6 V DC
20 mVpp
CPV10−... CPV14−...
40 mA
40 mA
96 mA
96 mA
278 mA
278 mA
21.6 ... 26.4 V DC
4 Vpp
CPV10−... CPV14−...
150 mA
233 mA
120 mA
158 mA
53 mA
75 mA
68 mA
90 mA
Watchdog function
active after approx.
40 ... 100 ms (see
3.5)
8 digital inputs
based on IEC 1131−2
type 2
24 V DC, PNP,
Status display (LED)
ON: 11 ... 30 V
OFF: −30 ... 5 V
0 V
typ. 3 ms (at 24 V)

Publicidad

loading

Este manual también es adecuado para:

Cpv ge-asi-8e6a-z m8 serie