Ribind K 2007 Manual De Instrucciones página 25

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

DIP 6 - Off The K BUTT, the PED BUTT button, the RADIO REMOTE buttons
perform:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely
opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED BUTT opens the
gate partially as described in Point D.
CLOCK fUNCTION
If you want the Clock function must request K2007 with firmware
04.
ATTENTION: A CLOCK CONNECTED TO K2007 with fw 05 or
more ACTIVATEs THE AUTOMATIC MOVEMENT Of THE GATE
WITHOUT HAVING THE PrOTECTION Of THE sAfETY DEVICEs!
The Clock Function is useful during rush hours, when traffic is heavy and the
flow is slow (e.g. entrance/exit of employees, emergencies in residential areas
or car parks and, temporarily, for removal vans) and it's necessary to keep the
gate opened.
CLOCK fUNCTION APPLICATION
It is necessary to request a K2007 control panel with firmware 04.
Select the automatic functioning DIP 6 Off.
It can be done by connecting a switch and/or a daily/weekly clock either in
parallel to the K BUTT button or instead of the K BUTT button. When the
control board receives this command, the gate will open and by keeping
this contact closed for all the time of the gate opening, the Clock Function is
automatically activated. In fact, once reached the open position, the gate will
remain opened and all of the control board functions are blocked. Only when
K BUTT contact is released, the control board functions are re-activated and
the Automatic Closing restarts (if enabled) doing the countdown to the gate
closing.
PEDEsTrIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for example, to
permit a pedestrian crossing. In fact, the Pedestrian command (see Point E) is
carried out only by opening the gate just enough for a pedestrian to pass, as
described into the Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled
or disabled with DIP3.
From the Pedestrian opening position, the gate can be completely opened by
the OPEN or by the K BUTT button or by the RADIO button.
AUTOMATIC CLOsING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning
ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOsING (from the PEDEsTrIAN open position)
The Automatic Closing from the pedestrian open position can be enabled
turning ON the DIP3. The maximum gap of time that can be programmed is 5
minutes (see Point E).
f
UNCTIONING Of sAfETY ACCEssOrIEs
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active both in
gate opening and in gate closing. In this configuration, if an obstacle cuts the
photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the
obstacle is removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in
gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still
if a close command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell
receivers must be connected in series.
In case the photocells are not installed, this contact must be short circuited with a
wire jump (from PHOT to COM) to permit the gate to operate.
sAfETY sTrIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2 seconds, is
performed. The gate interrupts any movement and this alarm state will be signalled
by both the Blinker and the Buzzer, if installed, which will remain on for 1 minute.
The normal gate operations can be restored by pressing any push button or radio
commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact. In case
there are more than one safety strip, all their contacts must be connected in series.
In case the safety strip is not installed, this contact must be short circuited
with a wire jump (from EDGE to COM) to permit the gate to operate.
TEsTING THE sAfETY sTrIP equipment
The DIP10 ON enables to test the safety strip equipment. The test is performed
every time the gate completes a full opening. The test is available only if the safety
strip device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the
A+TEST and A- outputs (DIP10 ON). Automatically, every time the gate completes
a full opening, just before closing, the control board switches OFF the A+TEST and
A- power supply output for a very short time. While the safety strip power supply is
switched OFF, if everything is working fine the safety strip contact (EDGE - COM)
must open. In case the test fails, no other gate manoeuvre will be allowed and the
alarm state will be signalled by both the Blinker and the Buzzer, if installed, which
will remain on for 5 minutes
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP10
MUST BE LEFT OFF.
sTOP BUTTON
If the Automatic command is enabled (DIP 6 OFF), a Normally Closed contact
could be connected in series to the COM wire of the opened and the closed limit
switches.
This contact works like a STOP button to interrupt any gate manouver.
fUNCTIONING IN DEAD MAN MODE WHEN THE sAfETY DEVICEs ArE
fAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if
photocell fails or remain engaded for more than 60 seconds, the K BUTTON and
PEDESTRIAN commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the
programming led.
With the blinking of the programming led, the opening and closing operation are
allowed only with the command button pressed and held. The radio commands
and that of automatic closing, will be excluded, since their use in this mode, is not
allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio
commands and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the
safety strips (or photocells) the photocells (or safety strips) still work by
interrupting the operation in progress.
The dead-man operation is only an emergency operation which must be
activated for a very short period and with the complete installation at sight
so to have a secure and safe control of the system. As soon as possible
however, the failing safety devices must be repaired and activated.
fLAsHING LIGHT
Connect the flashing light to J7 flashing light outputs, use flashing lights ACG7059
and bulbs of 40W maximum.
NB: This electronic K board can only supply power to FLASHING LIGHTS with
25
25
G
B

Publicidad

Tabla de contenido
loading

Tabla de contenido