900CT-101 FUNCTION TABLE
DESCRIPTION
- Keeps the previous configuration (if the control unit is new, the data are the
default ones)
- Upload default values
Gate opening time
Opening time of pedestrian gate
Gate closing time
Closing time of pedestrian gate
Pre-flashing time
- Pre-flashing disabled (it corresponds to 0)
Motor power
Start off
Slowed down starting time
- Slowed down starting disabled
Slow down time
- Slow down disabled
Start in opening
- Start command is not available
- Command close gate
- Stop the gate and goes in pause
Start in closing
- Start command stop the gate
- Start command open the gate
Start in pause
- Start command is not available
- Start command closes the gate
Pedestrian in opening
- Pedestrian start command is not available
- Pedestrian start command closes the gate
- Gate goes in pause
Automatic closing
- The gate closes after the setup time)
- The automatic closing is not active (it corresponds to 0)
Closing after passage
- Closing after passage disabled
- Gate stop for a time to be set between 0.5" to 20'
Pause after transit
Courtesy Light
- Lights start time adjustable from 0 to 20'
- Lights are on trough the whole cycle
- Auxiliary output
- Timed aux out (from 0 to 20')
- Aux out relay with bistable functioning
- Aux out relay with monostable functioning
Flashlight in pause
Operation modes
- Start inputs from terminal board are disabled
- Standard operation
- Separated opening and closing commands
- Manned operation
- Timer operation