Refurbishment Zone Transponder RZT 8000
3
Connecting terminals and jumpers
F1
X1
T1,25A
+12V
BR1
0V
X2
X7.2
+UL
Isolator
788612
-UL
out
X7
X7.1
-UL
in
V19
V18
Fig. 8 : Third-party detector connecting module (Part No. 80863x.10)
BR1, BR2
Detector zone voltage
BR1
BR2
Fuse T 1.25 A, 12 V DC external power supply
F1
Electronic protection device (Multifuse) of the relay outputs K1 and K2
F2, F3
To reset, remove voltage for approx. 30 seconds.
Freely programmable relay outputs for controlling external equipment
K1, K2
LED indicator for communication on the esserbus
V18, V19
Terminal +12V
X1
Terminal 0V
UL
X2
in
UL
UL
out
Screen
R1
X3
R1
Uext R1
R2
X4
R2
Uext R2
0V
G4
X5
G4
G3
G3
G2
X6
G2
G1
G1
Connector for optional zone isolator (Part No. 788612)
X7, X7.1, X7.2
Jumpers for programming
X10, X 11, X12
relay operating mode
X13, X 14, X15
20
X3
BR2
K1
BARCODE
Remove jumpers
when isolator is installed!
X5
open
open
Connection for external power supply
GND (same potential as 0V terminal X4)
(+)
®
(-)
esserbus
/ esserbus
(-)
Connector for cable screening
(-)
Connection of external equipment
(+)
(+)
Power supply for external equipment (ref. operating mode 2 and 3)
(-)
Connection of external equipment
(+)
Power supply for external equipment (ref. operating mode 2 and 3)
(+)
0V (same potential as 0V terminal X1)
(-)
detector zone 4
(+)
detector zone 4
(-)
detector zone 3
(+)
detector zone 3
(-)
detector zone 2
(+)
detector zone 2
(-)
detector zone 1
(+)
detector zone 1
X4
K2
X6
808630.10
24 V DC
®
®
-Plus Loop
Relay 1
30 V DC / 1 A or 48 V AC / 0,5 A
Relay 2
Modul index
808631.10
12 V DC
closed
closed
max. contact rating:
FB 789807.10 / 05.17