6.2

Operating mode 2 - relay monitoring with external power supply

When a relay is activated, the external supply voltage (e.g. 24 V DC) is switched through to the connected
external alarm device, e.g. on visual and/or audible alarm device.
Arrange jumpers (X10 to X15) for mode selection in accordance with Fig.
settings for relay output 1: jumpers X10, X11, X12
settings for relay output 2: jumpers X13, X14, X15
e.g. 24 V DC (ref. Technical specifications)
+UBext
-UBext
esserbus
transponder
®
+UB 12 V
GND
Jumper closed
Jumper open
Fig. 11 : Application example – operating mode 2 (relay monitoring with external power supply)
Terminals 0 V – terminal strips X1 and 0 V – terminal strip X4 are not galvanically isolated!
Max. contact load of relays K1 and K2: 30 V DC / 1 A or 48 V AC / 0.5 A
24
alarm device
F1
X1
T1,25A
+12V
BR1
0V
X7.2
Isolator
788612
X7.1
visual
1N4004
X3
BR2
K1
BARCODE
audible
alarm device
1N4004
X4
K2
FB 789807.10 / 05.17