3.2
Electrical data
Basis of the data
Mains
3/PE AC
3/PE AC
3/PE AC
Input data
Type
E94APNE1004
E94APNE2454
Temperature in the control cabinet
Type
E94APNE1004
E94APNE2454
Output data
Type
E94APNE1004
E94APNE2454
Temperature in the control cabinet
Type
E94APNE1004
E94APNE2454
Type
E94APNE1004
E94APNE2454
EDK94PNE245 DE/EN/FR/ES/IT 1.0
Voltage
U
[V]
LN
230
180 - 0 % ... 264 + 0 %
400
320 - 0 % ... 440 + 0 %
500
400 - 0 % ... 550 + 0 %
Voltage
Frequency
[V]
[Hz]
230/400/500
50/60
230/400/500
50/60
Voltage
[V]
230/400/500
230/400/500
Voltage
Frequency
[V]
[Hz]
325/565/705
0 (DC)
325/565/705
0 (DC)
Voltage
[V]
With mains filter P
325/565/705
27.9/48.6/60.8
325/565/705
68.5/119/149
Total (when operating with I
230
550
Technical data
Electrical data
Voltage range
U
[V]
LN
Current [A]
max. +45 °C
max. +55 °C
82/82/82
61/61/61
200/200/200
150/150/150
Continuous input power
S
[kVA]
L
32.6/56.7/70.9
79.6/138/173
Current [A]
max. +45 °C
max. +55 °C
100/100/100
75/75/75
245/245/245
184/184/184
Output power X109, X110, +UG, -UG
[kW]
Without mains filter P
aDC
Power loss P
[W]
V
)
Constant (control electronics only)
aNx
3
Frequency range
f [Hz]
45 - 0 % ... 65 + 0 %
45 - 0 % ... 65 + 0 %
45 - 0 % ... 65 + 0 %
Number of
phases
3
3
Number of
phases
2
2
[kW]
aDC
20.8/36.2/45.2
51/88.6/111
7
7
41