ELECTRICAL CONNECTION

• Before connecting the appliance make sure that the voltage and frequency rated on the data plate
conform to those of the mains supply.
WARNING! An omnipolar trip switch with a least 3mm between the contacts must be installed
between the unit and the mains supply.
• Connect the control and security device wires.
• Connect the power supply cable to the device using the terminal block (which is already connected to
the transformer primary, white wire).
• Do not use cables with aluminium conductors; do not solder the ends of cables which are to be inserted into the
binding posts; use cables which are marked T min 85°C and are resistant to atmospheric agents.
• The terminal wires must be positioned in such a way that both the wire and the insulating sheath are tightly
fastened. Where possible use the supplied cable clamp.
Terminal board connection (fig.1)
1-2
Motor 1 output
Opening: live at binding post "1" and negative at binding post "2"
Closing: Negative at binding post "1" and live at binding post "2"
3-4
Motor 2 output
Opening: live at binding post "3" and negative at binding post "4"
Closing: Negative at binding post "3" and live at binding post "4"
5
Common for all inputs and outputs
6
Output for electric locking device (continuously powered) 12Vdc - 15W; it must be garage door type lock
(not automatically resetting) as it is only activated for 1 second.
Voltage free output (contact normally open) for the night light (powered separately by: Vmax= 30Vac/dc;
7-8
Imax= 1A) or for the second radio channel. Selection is made during programming.
9
Indicator light output 24Vac 3W
10
24Vac 10W output warning lights (intermittent or continuous activation)
11
24Vac 10W output, powering external devices.
12-13
Common for all inputs and outputs
FCC1 (normally closed contact) closing travel limit switch leaf 1
14
15
FCA1 (normally closed contact) opening travel limit switch leaf 1
16
FCC2 (normally closed contact) closing travel limit switch leaf 2
FCA2 (normally closed contact) opening travel limit switch leaf 2
17
TAL (normally open contact) limited opening button
18
19
TA (normally open contact ) Opening button input
20
TC (normally open contact ) Closing button input
21
TD (normally open contact ) for the sequential command (open, block, close, block or open, close with travel
direction inversion only during closing according to the program settings).
22-23
Common for all inputs and outputs
24
TB (normally closed contact) blocking button input (The opening of this contact interrupts the cycle
until a new movement command is given)
FTC_I (normally closed contact) Safety and control devices in input (photocells invert the travel direction
25
when an obstruction is detected) The opening of this contact will provoke a travel direction inversion during
closure due to the cutting in of the safety device
26
FTC_S (normally closed contact) Safety and control devices in input (stop photoelectric cells). The
opening of this contact will block all movement, until the obstruction has been removed, due to
the safety device cutting in, the door will then continue moving until it reaches a travel limit (only
in the automatic mode).
27-28
Common for all inputs and outputs
29
Pole for radio receiver antenna; connect a 17cm piece of rigid wire or an external antenna ANS400 using
coaxial cable RG58 (with an impedance of 50Ω)
30
Mass for radio receiver antenna
Note: ALL UNUSED NORMALLY CLOSED CONTACTS MUST BE BRIDGED
(It is not necessary for travel limits excluded via software during programming)