Connections
+LOAD 1,2,3,4*
-LOAD 1,2,3,4*
EPS Fault
GEN Fault
+BATT
-BATT
* Depending upon model
Installation Instructions
This unit is only suitable for installation as permanently connected equipment. The PSU is NOT
SUITABLE for external installation. EQUIPMENT MUST BE EARTHED. Before installation, ensure that
external disconnect device is OFF. The PSU should be installed according to all relevant safety
regulations applicable to the application.
100mm
N E L
G1380xBM-S (4A, 5A)
Mounting
1)
Mount securely in correct orientation allowing minimum clearance – see diagram.
2)
Route mains and low voltage output cables via different knockouts and/or cable entry holes.
3)
Use bushes and cable glands rated to UL94 HB minimum.
Mains Power Up
4)
Attach correctly rated mains cable (minimum 0.5mm
5)
Apply mains power. Check for 13.8Vdc on load outputs. Check green Mains LED is on.
6)
Disconnect mains power.
Load Output
7)
Attach correctly rated load cable and fasten using cable ties. Note polarity.
8)
Apply mains power. Check green Mains LED is on.
9)
NOTE: Red LED may be illuminated to indicate that no battery has been connected. This is normal.
10) Verify load is operating correctly.
11) Disconnect mains power.
Standby Battery
12) Attach supplied battery cables to terminal block and battery.
NOTE: ensure correct polarity of battery connections: +ve use red lead, -ve use black lead.
13) Apply mains power. Check green Mains LED is on.
14) Check there is no fault indication on Red LED.
15) Disconnect mains power. Check that the batteries continue to supply voltage and current to the
load. The Green LED should be off.
NOTE: Batteries must have sufficient charge to supply the load
16) Reconnect mains power. Green LED should be on.
Technical Support Line +44 (0)2392 696638
© 2013 Elmdene International Ltd
+ve voltage output to load equipment
-ve voltage output to load equipment
Voltfree contacts for loss of mains indication
Voltfree contacts for general faults (see signalling outputs)
+ve (Red lead) connection to standby battery
-ve (Black lead) connection to standby battery
G13810BM-C (10A)
G1380xBM-y-s
100mm
L
E
N
2
[3A], 300/500Vac) and fasten using cable ties.
PAK200467
ssue 02C
Feb 2013