Tamper
19) Check that the tamper screw makes good contact with the mounting surface. Check that the tamper
switch is:
-
closed when the lid is closed and the lid screw is fitted
-
open when the lid is open.
20) Close cover and secure using fastening screw(s) provided.
Max Output Current to load
Output Fuse* (20mm glass)
Max Mains Input Current (at
90Vac)
Mains Input Fuse
(20mm 250Vac HBC)
Battery Fuse Protection
* Single o/p models only
Operating Instructions
This unit is intended for use by Service Personnel only. There are NO USER SERVICEABLE parts
inside.
The green Mains LED will be illuminated whilst the mains supply is present. In the event of a fault
condition the red Fault LED will flash and the corresponding (EPS or GEN) fault signal contacts will open.
Maintenance
There is no regular maintenance required of the PSU other than periodic testing and replacement of the
standby battery. Reference should be made to the battery manufacturer's documentation to
determine typical/expected battery life with a view to periodic replacement of the battery.
If the output of the PSU fails, the cause of the failure should be investigated e.g. short circuit load. The
fault should be rectified before restoring power to the PSU. The fuses may need to be replaced. Ensure
the correct fuse rating and type is used.
Risk of explosion if battery is replaced by an incorrect type.
Dispose of used batteries according to the battery manufacturer's
instructions and all local and national regulations.
The packaging supplied with this product may be recycled.
Specifications subject to change without notice
Technical Support Line +44 (0)2392 696638
© 2013 Elmdene International Ltd
Model Specification Table
G13804BM
4A
F4.0A
1.3A
T2.0A
F4.0A
CAUTION
Please dispose of packaging accordingly.
G1380xBM-y-s
G13805BM
G138010BM
5A
F5.0A
1.5A
T2.0A
F5.0 A
PAK200467
ssue 02C
2 x 5A
2 x F5.0A
3.0A
T3.15A
2 x F5.0A
Feb 2013