Datos Técnicos Mk7; Technical Data Mk7; Datos De Pedido; Ordering Details - Bender ISOMETER IR427 + MK7 Manual De Instrucciones

Tabla de contenido

Publicidad

Datos técnicos MK7
Coordinación de aislamiento conforme a
IEC 60664-1 / IEC 60664-3
Tensión de diseño....................................................................................................................... 50 V
Tensión nominal de choque/grado de contaminación ................................................... 500 V / III
Tensión de alimentación
Tensión de alimentación U
........................................................................................ 18...28 V CC
s
Consumo propio .................................................................................................................... 0,5 VA
Medio ambiente/EMC
EMC ................................................................................................................................... IEC 61326
Temperatura de funcionamiento ........................................................................ -10 °C...+55 °C
Clases climáticas conforme a IEC 60721:
Uso estacionario (IEC 60721-3-3) ........................... 3K5 (sin condensación y formación de hielo)
Transporte (IEC 69721-3-2) .................................... 2K3 (sin condensación y formación de hielo)
Almacenamiento prolongado (IEC 60721-3-1) ..... 1K4 (sin condensación y formación de hielo)
Resistencia mecánica conforme a IEC 60721:
Uso estacionario (IEC 60721-3-3) ............................................................................................ 3M4
Transporte (IEC 60721-3-2) ..................................................................................................... 2M2
Almacenamiento prolongado (IEC 60721-3-1) ...................................................................... 1M3
Conexión
Tipo de conexión........................................................................ Terminales de tornillo
Capacidad de conexión:
Rígida/flexible .............................................................................. 0,2...2,5 mm
Flexible con virola de cable .......................................................... 0,2...1,5 mm
Longitud de desaislamiento ................................................................................................... 8 mm
Otros:
Modo de funcionamiento ....................................................................... Funcionamiento continuo
Posición de uso ................................................................................................................ cualquiera
Clase de protección piezas montadas (IEC 60529) ................................................................... IP30
Clase de protección terminales (IEC 60529) ............................................................................. IP20
Color placa frontal ....................................................................................................... blanco alpino
Caja empotrada, diámetro (en el volumen de suministro).................................................. 66 mm
Peso (con bastidor de inserción) ............................................................................................... 80 g

Datos de pedido

Tipo Tensión de alimentación U
IR427-2
70...264 V CA, 42...460 Hz
MK7
18...28 V CC
*Valores absolutos del rango de tensión
STW2 Toroidal de medida de corriente
ES0107 Sensor de temperatura, PTC
XM420 Bastidor de inserción
Caja de pared hueca MK, diámetro 67 mm
IR427-MK7_D00118_00_M_ESEN / 09.2016
2
(AWG 24...14)
2
(AWG 24...16)
= U
*Ref.
s
n
B 7207 5300
B 9510 0201
B 942 709
B 924 186
B 990 994
B 9510 0203

Technical data MK7

Insulation coordination acc. to
IEC 60664-1 / IEC 60664-3
Rated insulation voltage ............................................................................................................ 50 V
Rated impulse voltage/pollution degree ......................................................................... 500 V / III
Supply voltage
Supply voltage U
...................................................................................................... DC 18...28 V
S
Power consumption .............................................................................................................. 0.5 VA
Environment / EMC
EMC ................................................................................................................................... IEC 61326
Operating temperature ........................................................................................ -10 °C...+55 °C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ......................... 3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) ................................. 2K3 (except condensation and formation of ice)
Storage (IEC 60721-3-1) .................................... 1K4 (except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................................................................ 3M4
Transport (IEC 60721-3-2) ........................................................................................................ 2M2
Storage (IEC 60721-3-1) ........................................................................................................... 1M3
Connection
Connection type............................................................................ screw-type terminals
Connection properties:
rigid / flexible ............................................................................... 0.2...2.5 mm
flexible with connector sleeve ..................................................... 0.2...1.5 mm
Stripping length ...................................................................................................................... 8 mm
General data:
Operating mode ............................................................................................. continuous operation
Position of normal use ................................................................................................................ any
Degree of protection, internal components (IEC 60529) ......................................................... IP30
Degree of protection, terminals (IEC 60529) ............................................................................ IP20
Front plate colour ......................................................................................................... alpine white
Flush-mounting enclosure, diameter (included in the scope of delivery) ......................... 66 mm
Weight (including mounting frame) ........................................................................................ 80 g

Ordering details

TypeSupply voltage U
= U
*Art. No.
s
n
IR427-2
AC 70...264 V, 42...460 Hz
MK7
DC 18...28 V
*Absolute values of the voltage range
STW2 Measuring current transformer
ES0107 Temperature sensing element, PTC
XM420 Mounting frame
MK-cavity-wall-box, diameter 67 mm
ISOMETER® IR427 + MK7
2
(AWG 24...14)
2
(AWG 24...16)
B 7207 5300
B 9510 0201
B 942 709
B 924 186
B 990 994
B 9510 0203
11

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Isometer ir427Mk7