Dip Switch Settings - Risco Industrial LuNAR DT AM Grade 3 Guia De Instalacion

Detector para montaje en techos altos
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

EOL
RESISTORS
JUMPERS

DIP Switch Settings

The Industrial LuNAR DT AM Grade 3 has a 9 position DIP switch that changes functionality for
use in Relay mode or in BUS operation mode. Set the DIP switch according to the tables below:
Factory Default Settings:
16
FAULT/AM EOL
JUMPERS
12K
No
Resistor
(Default)
Schematic of EOL Resistors
ON
1
2
3
4
5
6
7
Industrial LuNAR DT AM Grade 3 Installation Guide
The jumpers are used when connecting the
detector to a DEOL or TEOL Zone. The jumpers
allow the selection of TAMPER, ALARM E.O.L
resistors (1K, 2.2K, 4.7K, 5.6K or 6.8K), according
to the control panel settings. An additional double
jumper allows the connection of 12K FAULT/AM
E.O.L resistor (see EOL Resistors Schematic).
Follow the terminal block connection diagram
when connecting the detector to a Double/Triple
End Of Line (DEOL/TEOL) Zone.