9 – Start-Up, Shutdown and Bypass
9-10 Manual Bypass Procedure (Parallel UPS)
•
If the UPS systems have external battery cabinets connected,
5
switch off the external battery cabinet circuit breaker switch
each battery pack.
•
In this mode, only the output circuit breaker switch
6
terminal block
B
service personnel to perform maintenance or repair. Note:
Qualified service personnel may prefer to de-energize the UPS
systems completely, depending on local codes and the nature of the
maintenance or repair.
9-11 Switching from Manual Bypass to Normal Mode (Parallel UPS)
•
If the UPS systems have external battery cabinets connected,
1
switch on the external battery cabinet circuit breaker switch
each battery pack.
•
2
Switch on the bypass input circuit breaker switch
circuit breaker switch
•
Confirm that the LCD screens of both UPS systems read "ON
3
MANUAL BYPASS", then switch off the manual bypass input
circuit breaker switch
will read "ON AUTO BYPASS".
•
Switch on the main input circuit breaker switch
4
system.
•
5
Press the ON button
(until you hear a beep), then release the button. Press the ON
button for the second UPS system for 3 seconds (until you hear
a beep), then release the button. When the inverter of each UPS
system is operating normally, they will switch to online (normal)
mode at the same time.
Output
4
200706017 93-2688 SU manual 4C.indd 31
200706017 93-2688 SU manual 4C.indd 31
A
contain hazardous voltage, allowing qualified
A
and the output
of each UPS system.
B
A
of each UPS system. The LCD screen
A
of each UPS
A
of the first UPS systems for 3 seconds
A
Manual
Bypass
Main
Bypass
Input
Input
(continued)
(continued)
A
of
5
and the
A
6
of
A
1
B
Output
2
Output
3
5
31
A
B
A
A
Manual
Bypass
Main
Bypass
Input
Input
A
Manual
Bypass
Main
Bypass
Input
Input
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
11/29/2007 2:02:50 PM
11/29/2007 2:02:50 PM