Installing Bc Controller; Checking The Accessories With Bc Controller; Installing Bc Controllers; Connecting Refrigerant Pipes And Drain Pipes - Mitsubishi Electric CMB-P-V-GB Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 19
Item
Total piping length
Longest piping length
Between outdoor unit and master
BC controller
Between indoor units and master
BC controller
Above outdoor unit
Between
indoor and
Below outdoor unit
outdoor units
Between indoor units and slave
BC controller
Between indoor units
Between slave BC controller and master
BC controller

3. Installing BC controller

3.1. Checking the accessories with BC con-
troller
The following items are supplied with each BC controller.
Item
1
Drain hose
2
Tie band
3
Hose band
4
Reducer (large & small)
5
Refrigerant connection pipe

4. Connecting refrigerant pipes and drain pipes

4.1. Connecting refrigerant pipes

1. Connect the liquid and gas pipes of each indoor unit to the same (correct) end
connection numbers as indicated on the indoor unit flare connection section of
each BC controller. If connected to wrong end connection numbers, there will
be no normal operation.
2. List indoor unit model names in the name plate on the BC controller control
box (for identification purposes), and BC controller end connection numbers
and address numbers in the name plate on the indoor unit side.
3. If the number of connected indoor units is less than the number of branch
holes, it does not matter which end connections you leave.
Seal unused end connections using flare nuts with end caps just as they were
capped when shipped from the factory. No end cap will lead to refrigerant leak-
age.
4. When using branch pipes (CMY-Y102S-G), be sure to connect them level.
5. Be sure to tighten the flare nuts using a double spanner. Otherwise the refrig-
erant may leak.
6. Be sure to use non-oxidative brazing where necessary. If you do not use non-
oxidative brazing, it may clog the pipes.
7. After completing pipe connection, support the pipes to ensure that load is not
imparted to the BC controller's end connections (particularly to the gas pipes
of indoor units).
Warning:
When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant (R410A) specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-
function and result in severe damage.
6
(Unit: m)
Piping portion Allowable value
A+B+C+a+b
Below 300 *1
+c+d+e
A+C+e
Below 150
A
Below 110
C+e
Below 40 *2
H
Below 50
H1
Below 40
Below 15
h1
(Below 10)*3
h2
Below 15*3
h3
Below 15*3
Qty
1
1
1
Same number as
branch holes
8
Notes:
*1 Please refer to the figure "Allowable Pipe Length", below when the total
piping length exceeds 300 m.
*2 Please refer to the figure "Distance between master BC controller and
farthest indoor unit" when the distance between master BC controller
and farthest indoor unit exceeds 40 m.
*3 10 m or less, with indoor units with model numbers of 125, 140.
*
It is possible using a master BC controller and two slave BC controllers.
(Two slave BC controllers connect in parallel.)
*
It cannot use only slave BC controller.
Allowable pipe length
400
350
300
250
200
30
40
50
60
70
80
90
100
110
Distance between outdoor unit
and master BC controller (m)

3.2. Installing BC controllers

Installing hanging bolts
Install locally procured hanging bolts (all screws) following the procedure given in
the figure. The hanging bolt size is ø10 (M10 screw).
To hang the unit, use a lifting machine to lift and pass it through the hanging bolts.
[Fig. 3.2.1] (P.2)
1 Hanging method
A: Min.30 mm
A Hanging bolt ø10 (field supply)
C Washer (field supply)
E Anchor bolt M10 (field supply)
s Be sure to install the BC controllers level. Installing obliquely may cause
a risk of drain leakage. Use a level to check the unit's level. If it is oblique,
loosen the fixing nut and make an adjustment.
Caution:
Be sure to install the unit body level.
Caution:
Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 "Copper and copper alloy seamless
pipes and tubes". In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-
ing particles, oils, moisture, or any other contaminant.
Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil
in the existing piping will cause the new refrigerant to deteriorate.
Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.
- The refrigerant used in the unit is highly hygroscopic and if it mixes with
water it will degrade the refrigerator oil.
1. Size of BC controller's end connection piping
[Fig. 4.1.1] (P.3)
Piping portion
High pressure
Total capacity
(liquid) side
of indoor units
Below 200
ø15.88 (Brazing) ø19.05 (Brazing)
201 to 300
ø19.05 (Brazing)
301 to 350
Indoor unit side
ø9.52 (Flare)
Distance between master BC
controller and farthest indoor unit
70
60
50
40
30
20
10
0 0
5
10
15
Height difference between
BC controller and farthest
indoor unit (m)
2 Installing-on-the-floor method
B Nut (field supply)
D Double nuts (field supply)
(Unit: mm)
Low pressure
Liquid side
(gas) side
ø9.52 (Brazing)
ø22.2 (Brazing)
ø28.58 (Brazing)
ø12.7 (Brazing)
ø15.88 (Flare)

Publicidad

Tabla de contenido
loading

Tabla de contenido