Description
Param.
P0237 AI2 Gain
P0238 AI2 Signal Type
P0239 AI2 Offset
P0240 AI2 Filter
P0241 AI3 Signal Function
P0242 AI3 Gain
P0243 AI3 Input Signal
P0244 AI3 Offset
P0245 AI3 Filter
P0246 Freq. Input FI
P0247 FI Gain
P0248 Min. FI
P0249 FI Offset
P0250 Max. FI
P0251 AO1 Function
P0252 AO1 Gain
P0253 AO1 Signal Type
P0254 AO2 Function
P0255 AO2 Gain
Quick Reference of Parameters, Alarms and Faults
Adjustable
Range
0.000 to 9.999
See options in P0233
-100.0 to 100.0 %
0.00 to 16.00 s
See options in P0231
0.000 to 9.999
0 = 0 to 10 V / 20 mA
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
4 = -10 V to +10 V
-100.0 to 100.0 %
0.00 to 16.00 s
0 = Inactive
1 = Active
0.000 to 9.999
10 to 20000 Hz
-100.0 to 100.0 %
10 to 20000 Hz
0 = Speed Ref.
1 = Not Used
2 = Real Speed
3 = Not Used
4 = Not Used
5 = Output Current
6 = Process Var.
7 = Active Current
8 = Not Used
9 = PID Setpoint
10 = Not Used
11 = Motor Torque
12 = SoftPLC
13 = Not Used
14 = Not Used
15 = Not Used
16 = Motor Ixt
17 = Not Used
18 = P0696 Value
19 = P0697 Value
20 = P0698 Value
21 = Function 1 Application
22 = Function 2 Application
23 = Function 3 Application
24 = Function 4 Application
25 = Function 5 Application
26 = Function 6 Application
27 = Function 7 Application
28 = Function 8 Application
0.000 to 9.999
0 = 0 to 10 V
1 = 0 to 20 mA
2 = 4 to 20 mA
3 = 10 V to 0
4 = 20 to 0 mA
5 = 20 to 4 mA
See options in P0251
0.000 to 9.999
Factory
User
Properties Groups
Setting
Setting
1.000
0
0.0 %
0.00 s
0
cfg
1.000
0
0.0 %
0.00 s
0
1.000
10 Hz
0.0 %
10000 Hz
2
1.000
0
5
1.000
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
MW500 | 11

Publicidad

loading