DIP SWITCH CONFIGURATION
Turn off the power to the unit.
To be performed in the installation phase, only by expert staff.
SW2 contains settings that must not be modified (the table states default settings).
By acting on the Dip-Switches of SW1 the following functionalities are obtained:
SW 2
Dip 1 (Default OFF)
Factory settings.
Dip 2 (Default OFF)
Factory settings.
Dip 3 (Default OFF)
Factory settings.
Dip 4 (Default OFF)
Factory settings.
Dip 5 (Default OFF)
Factory settings.
Dip 6 (Default OFF)
Factory settings.
Dip 7 (Default OFF)
Factory settings.
Dip 8 (Default ON)
Factory settings.
SOME EXAMPLES :
FCL 2 pipe (default)
1 2 3 4 5 6 7 8
FCL 2 pipe + Electric heater
1 2 3 4 5 6 7 8
FCL 4 pipe
1 2 3 4 5 6 7 8
FCL 4 pipe + Electric heater
1 2 3 4 5 6 7 8
OFF
ON
SW2
OFF
ON
SW2
OFF
ON
SW2
OFF
ON
SW2
SW 1
Dip 1 (Default OFF)
Resistance control:
- functioning in integration mode, OFF
- functioning in replacement mode, ON.
Dip 2 (Default OFF)
Presence of the resistance:
- without electric heater, OFF,
- with electric heater, ON.
Dip 3 (Default OFF)
System type:
- 2 pipes (FCL32 - FCL 36 - FCL 42 - FCL 62), OFF
- 4 pipes (FCL34 - FCL 38 - FCL 44 - FCL 64), ON.
Dip 4 (Default OFF)
Factory settings.
Dip 5 (Default OFF)
Factory settings.
Dip 6 (Default OFF)
Ventilation control:
- continuous ventilation, OFF
- thermostat ventilation heating mode, ON.
Dip 7 (Default ON)
Factory settings , ON.
Dip 8 (Default ON)
Factory settings , ON.
1 2 3 4 5 6 7 8
SW1
1 2 3 4 5 6 7 8
SW1
1 2 3 4 5 6 7 8
SW1
1 2 3 4 5 6 7 8
SW1
OFF
ON
OFF
ON
OFF
ON
OFF
ON