Communication Parameters - Vortice VORT HR 450 Avel D Manual De Instrucciones

Ocultar thumbs Ver también para VORT HR 450 Avel D:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 96
ENGLISH

Communication parameters

Enter into the "modbus" sub-menu from menu 23 to edit the following parameters relative to the RS485#2:
Slave Address: from 1 to 254, default 1
Baud Rate: 9600/19200, default 9600
Parity: NONE
Commands
Read Coil (Function Code = 01 )
Read Holding Registers (Function Code = 03 )
Read Input Register (Function Code = 04 )
Write Multiple Coils (Function Code =15 )
Write Multiple Holding Registers (Function Code = 16 )
Parameters map
VARIABLE
ON/OFF
OPERATING SPEED
SETPOINT 1 TEMPERATURE
(SP1) - BYPASS
SETPOINT 2 TEMPERATURE
(SP2) - POSTHEATER
SUPPLY SPEED 1 (V1S)
SUPPLY SPEED 2 (V2S)
SUPPLY SPEED 3 ((V3S)
SUPPLY SPEED 4 ((V4S)
(SE ESISTENTE)
EXHAUST SPEED 1 (V1H)
EXHAUST SPEED 2 (V2H)
EXHAUST SPEED 3 (V3H)
EXHAUST SPEED 4 (V4H)
TIME PERIOD ENABLE
MINIMUM PERMITTED
SPEED (VMIN)
MAXIMUM PERMITTED
SPEED (VMAX)
RELATIVE HUMIDITY HR% 16BIT-INT
AIR QUALITY VOC
TEMPERATURE NTC 1
TEMPERATURE NTC 2 (EST) 16BIT-INT
TEMPERATURE NTC 3
TEMPERATURE NTC 4
ACTIVE BYPASS
ACTIVE NOFROST
ACTIVE POSTHEATER
ALARM PRESENCE
168
TYPE
BOOL
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
BOOL
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
16BIT-INT
BOOL
BOOL
BOOL
16BIT-INT
PERMITTED VALUES
TRUE, FALSE
1,2,3,4
16 ÷ SP2
SP1 ÷ 30
VMIN ÷ V2S
V1S ÷ V3S
V3S ÷ VMAX
VMIN ÷ V2H
V1H ÷ V3H
V2H ÷ V4H
V3H ÷ VMAX
TRUE, FALSE
0 ÷ VMAX
VMIN ÷ 100
0 ÷ 100
0 ÷ 100
-40 ÷ 60
-40 ÷ 60
-40 ÷ 60
-40 ÷ 60
TRUE,FALSE
TRUE,FALSE
TRUE,FALSE
(*)
READ/WRITE
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
R
R
R
R
R
R
R
R
R
R
R
R
ADDRESS
16399
16400
16401
16402
16403
16404
16405
16406
16407
16408
16409
16410
16411
8961
8964
8974
8975
8976
8977
8978
8979
8981
8982
8983
8984

Publicidad

Tabla de contenido
loading

Tabla de contenido