HBS 200 (347-480V) Product Overview
347/480
PIR
VAC
60Hz
Product description
The HBS 200 (347-480V) sensor
provides effective lighting control
in high bay aisle way applications.
The sensor contains two dual-
element pyroelectric detectors and is
Specifications
Voltage
347/480 VAC, 60 Hz
Load rating
5A electronic ballast load
Time delay
15 sec to 30 min
Light level
.2 - 200 footcandles; 2 - 2000 lux
Coverage
100 x 13 ft (30.48 x 3.96 m) linear detection
Environment
IP20 rated, -4°F to +122°F, -20°C to +50°C
Dimensions
3.9 x 3.9 x 2.6 in; 99 x 99 x 66 mm
nipple length .62 in (15.75 mm)
5 year warranty
UL and CUL Listed, RoHS Compliant
1
2
5
ON
High
Low
1 2 3 4
4
3
1/2 inch threaded nipple
Light level trimpot
1
4
Lock nuts
Detection lens
2
5
Time delay setting DIP switch
3
Fixture
Aisle
or J Box
IP20
way
Mount
engineered to perform at a wide range
of mounting heights, up to 45 feet. It
mounts directly to a high bay lighting
fixture, or to a junction box.
Aisle
LC3
10ft/3m
20ft/6.1m
30ft/9.1m
40ft/12.2m
50ft
50ft
15.2m
15.2m
53ft
53ft
16.2m
16.2m
radial
tangential
The HBS 200 (347-480V) has an
aisle way coverage of up to 100 feet
when mounted at 40 ft.
- 4 -
Mounting
Placement guidelines
• The HBS 300 (347-480V) and HBS
200 (347-480V) lens must have
a clear, unobstructed view of the
detection area.
• Sensor should be 6 to 8 feet away
from heating/cooling supply ducts.
End of fixture mounting
The HBS 300 (347-480V) and HBS
200 (347-480V) typically mount to a
1/2" knockout at the end of a high/
low bay lighting fixture. The sensor's
lens should be mounted below the
bottom edge of the fixture.
The EM 1 Extender Module is
recommended if the knockout at the
end of the fixture is located greater
than 1/2" from the bottom edge of
the fixture.
Junction box mounting
If mounting to the end of a fixture
is not possible, the HBS 300 (347-
480V) and HBS 200 (347-480V) can
be mounted to any junction box
with a 1/2" (trade size) knockout.
This may be necessary if the fixture
location of the control area has an
obstruction that would block the view
of the sensor (for example: racking is
directly beneath the fixture).
• Ideal mounting height is up to 45 feet.
• Sensor must be mounted on a stable
platform.
Fixture
HBS sensor
Fixture
EM 1
HBS sensor
Junction
box
HBS sensor
- 5 -