Daitsu XK46 Manual Del Usuario página 33

Controlador por cable
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

finish setting.
(3) Press ENTER/CANCEL button to return to last step until exists setting
parameters.
The parameter setting list is as following:
Parameter
Parameter name
code
Set master indoor
P10
unit
Set infrared
P11
receiver of wired
controller
Set address of
P13
wired controller
Table 5.2 Parameter setting list
Parameter
range
00: do not change
current master/slave
state of indoor unit
01: set current indoor
unit as master indoor
unit
00: forbidden
01: activated
01: master wired
controller
02: slave wired
controller
27
Wired Controller XK46
Default
Note
value
When set the corresponding
indoor unit of wired controller
00
as master indoor
unit,"MASTER" icon will be
bright after finishing setting.
It can be set only through
master wired controller.
When infrared receiver of
wired controller is forbidden,
01
the wired controller can't
receive the signal from
remote controller and it is
operated through buttons.
When two wired controllers
control one indoor unit (or
several indoor units), the
addresses of the two wired
01
controllers should be
different. Assistant wired
controller (02) is without unit
parameter setting function
except setting its address.

Publicidad

Tabla de contenido
loading

Tabla de contenido