Energy Saving System Pump Control; Hydraulic Circuit Content; Hydraulic Data; Production Of Domestic How Water Dhw - emmeti EH Serie Manual De Instalacion Y Uso

Ocultar thumbs Ver también para EH Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

II.6.2

ENERGY SAVING SYSTEM PUMP CONTROL

The unit manages the pump unit, striving for the highest energy
savings. When the machine reaches the set point and the regulator
detects that the thermal/cooling load is null, the pump is turned off for a
set time (10'). Following regular intervals of time (10'), the pump is
turned back on for some seconds (60"). If, in these situations, it is
necessary to activate the compressor, the unit starts generating
heating/cooling capacity again. Otherwise, the pump is turned off to wait
for the following cycle. The times can be changed from a parameter
under the maintenance menu (see the manual of the electronic control).
II.6.4

HYDRAULIC DATA

Model
Safety valve calibration of channelled water.
Heat exchanger water content
Expansion tank capacity
Expansion tank pre-load
Expansion tank maximum pressure
Minimum water flow
The expansion tank on the machine has limited capacity to protect the hydraulic circuit inside the machine. It is the installer's duty to size and install an
expansion tank that is suitable for the system.
II.6.5

PRODUCTION OF DOMESTIC HOW WATER DHW

For the production of DHW by using the heat pump, use a technical water storage, which cannot be used directly for human consumption, and combine
it to a DHW producer.
The figure shows an example:
II.6.5.1
Management of the priorities and domestic hot water request
The priority between DHW and system can be set directly from the control panel.
How to manage the DHW request:
o by means of the digital input: the request is assigned by a thermostat assembled by the installer. When the thermostat closes, the unit understands
that there is a DHW request and, once the conditions have been verified, the procedure is activated to meet the DHW requirements;
o by means of temperature probe in the storage tank: a temperature probe is placed inside the storage tank, which is directly connected to the unit
board. The required set point can be configured from the panel together with the relative activation differential. In this case, the probe must be
accurately positioned and the maximum distance allowed respected due to the type of probes used.
Type of probe
description
type of probe
NTC150
NTC OT150
NTC
NTC
features
(25/85)
50k @25°C
3977 (±1%)
10k @25°C
3435 (±1%)
SECTION II: INSTALLATION AND MAINTENANCE
II.6.3

HYDRAULIC CIRCUIT CONTENT

For proper unit operation, a minimum amount of water must be ensured
in the hydraulic system. The minimum water content is established on
the basis of the unit's nominal cooling capacity (table A1 Technical
Date), multiplied by the coefficient expressed in l/kW.
Range
EH1819T-DC – EH2519T-DC – EH3019T-DC
If the amount of water in the system is less than the indicated amount,
install an additional storage tank.
EH1819
barg
6
l
1,9
l
0,5
barg
1
barg
10
l/h
1450
29
Specific capacity
2 l/kW
EH2519
EH3019
6
6
2,2
2,2
0,5
0,5
1
1
10
10
1450
1450
ACT
technical water storage
tank
ACS
instantaneous domestic
hot water producer
1 from heat pump
2 from the mains
3 drain
4 recirculation pump
5 DHW utility
6 from the mains
7 safety valve

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Eh1819t-dcEh2519t-dcEh3019t-dc

Tabla de contenido