Heating Installation With Zone Valves/Pumps And External Boiler (I3/I4) - Sime RVA 47.320 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring diagram
KEY
SM
Cascade delivery temperature feeler (QAD21)
SR
Cascade return temperature feeler (QAD21)
SE
External temperature feeler (QAC31)
SB
Boiler temperature feeler
PI
Installation pump
TA
Room thermostat
R2
562-Ohm-resistor
R3
604-Ohm-resistor
R4
649-Ohm-resistor
R4
Scheda caldaia
Scheda caldaia
Main PCB
SB
SB
SE
SE
CR
+
CR
ALBATROS
TA
TA
Connettore inserito
Connector inserted
N
T
L
CALDAIA 1
BOILER 1
3.3.3
Parameter setting
For the regulator to be able to recognize this installation you need to
set the following parameters as shown in the table.
Installation ID
– Setting mode = INSTALLER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
140
LPB address
148
Timer
170
H1 input management
173
Function of contact connected to H1
NOTE: In the case of non-condensation boilers, the return temperatu-
re must be raised in order to avoid the problems related to the flue
gas condensate. To do so, the OEM 22 parameter must be modified.
– Setting mode = MANUFACTURER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
22
Min. limit of cascade return temperature
3.3.4
Verifying the correct recognizing
To make sure the regulator has correctly recognized the installation on
the basis of the input parameters, display the "Installer" parameter on
line 53.
Installation n° 36 must appear.
PPS BUS
N
L
R3
Scheda caldaia
Main PCB
Main PCB
SB
SB
SB
SB
SE
SE
SE
SE
CR
CR
+
CR
CR
TA
ALBATROS
ALBATROS
TA
TA
TA
Connettore inserito
Connector inserted
Connettore inserito
Connector inserted
CALDAIA 2
CALDAIA 3
BOILER 2
BOILER 3
Default
Setup RVA :
values
Master
Slave
1
1
3
3
0
1
1
0
Default values
Setup
8°C
20°C
+
RVA 47.320 (SLAVE)
R2
R4
Scheda caldaia
Main PCB
SB
SB
SE
SE
CR
+
+
CR
ALBATROS
TA
TA
Connettore inserito
Connector inserted
CALDAIA 1
BOILER 1
(combinata)
(combined)
3.4
HEATING INSTALLATIONS WITH ZONE
VALVES/PUMPS AND EXTERNAL BOILER (I3/I4)
Characteristics in outline:
– Cascade management of up to 4 boilers
– Continuous power modulation of the entire cascade with automa-
tic management of the switching on/off of the single modules.
– Self-adjusting to the heat requirements.
– Automatic turnover of the boiler sequence.
– Automatic Summer/Winter switching.
– Climate adjustment with external feeler.
2
– The boilers are activated only by a signal from at least one zone
1
room thermostat.
-
– The installation pump is activated only by a signal from at least
-
one zone room thermostat.
– 7-day heating program option.
– On/Off switching of sanitary hot water production through a but-
ton on the regulator.
– 7-day Managing/Programming option for sanitary hot water.
– Automatic management of the Heating/Hot water production
priority.
The components of the kit to be used are:
Code
Description
RVA 47.320 Central unit for controlling boiler cascade
QAC31
External temperature feeler
QAD21
Feelers for delivery/return temperature of cascade
QAZ21
Boiler temperature feeler
––
"Albatros" jumper for configuration
––
4 stickers for boiler numbering (kit)
––
4 configuration resistors (kit)
NOTE: The relays for managing the heating requirement signals of the
various zones, which are shown in the wiring diagrams, are not included
in the supplied kits for cascade management.
LPB BUS
SM
SE
SR
TA
+
RVA 47.320 (MASTER)
PI
DO NOT REVERSE THE PPS CONNECTION POLARITY
Non invertire la polarità della connessione PPS
R3
Scheda caldaia
Main PCB
Scheda caldaia
Main PCB
SB
SB
SE
SE
CR
+
CR
ALBATROS
TA
ALBATROS
TA
Connettore inserito
Connector inserted
CALDAIA 2
CALDAIA 3
BOILER 2
BOILER 3
4 boilers 6 boilers
ES
ENG
FR
PPS BUS
BE
R2
SB
SB
SE
SE
CR
+
CR
TA
TA
Connettore inserito
Connector inserted
Quantity up to
1
2
1
1
2
2
1
1
4
6
1
2
1
2
39