Failure Information And Code - EAS ELECTRIC ECH R32 Serie Manual De Instalación Y Usuario

Ocultar thumbs Ver también para ECH R32 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5 FAILURE INFORMATION AND CODE

5.1 Failure code of unit
NO.
Code
Main control parameter memory EPROM failure
1
E0
Phase sequence failure of main control board check
2
E1
Communication failure between master and the HMI
3
E2
Communication failure between master and slave
Total water outlet temperature sensor failure (main unit valid)
4
E3
Unit water outlet temperature sensor failure
5
E4
1E5 condenser tube temperature sensor T3A failure
6
E5
2E5 condenser tube temperature sensor T3B failure
Ambient temperature sensor failure
8
E7
Power supply phase sequence protector output error
9
E8
Water flow detection failure
10
E9
1Eb-->Taf1 cooling evaporator low-temperature
12
Eb
antifreeze protection sensor failure
2Eb-->Taf2 cooling evaporator low-temperature
antifreeze protection sensor failure
Slave unit module reduction
13
EC
1Ed-->A system discharge temperature sensor failure
14
Ed
2Ed-->B system discharge temperature sensor failure
Unit water return temperature sensor failure
16
EF
System self-check failure alarm
17
EH
Discharge temperature sensor failure alarm
19
EP
Tz/7 Coil final outlet temperature sensor error
20
EU
System high-pressure protection or discharge
21
P0
temperature protection
Content
39
Note
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure recovery
Recovered upon failure rcovery
Recovered upon failure recovery
If there is a failure recovery,the
number of previous protections
will be cleared
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Recovered upon error recovery
Occurs 3 times in 60 minutes and
the error can be recovered by
turning off the power supply only
V.1

Publicidad

Capítulos

Tabla de contenido
loading