The control panel detects failure of the
unit and then alarms and shuts down.
Mains failure. The unit cannot start up. There is no start signal. Inspect and
Failure of
Mains is normal, but the unit can not
control
panel
shut down.
RS485 failure

4.4 Generator Trouble Shooting

4.4.1 Self-excited AVR - OFF LOAD
Trouble
symptom
Voltmeter
connected or faulty.
Connections are loose, broken or
corroded.
There is no residual magnetism in the
laminated steel core of the exciter
No voltage
stator.
(no load)
When
magnetism gives excitation to provide
sufficient sensing voltage (at least
3.5V) to power a self-excited AVR.
The
disappear in the following cases:
1、Long time storage.
2 、 "Flashing" with wrong battery
Table 4-4 Fault Finding: Self-excited AVR-Off Load
The probable reason
of
the
panel
generator
starts,
residual
magnetism
Troubleshoot, and restart after reset.
troubleshoot.
The instruments of the self-starting engine must
be power-on and work in auto mode.
The control wiring is wrong. Inspect and
Correct.
The instruments of the self-starting engine
malfunction. Service or replace.
Cooling operation for 3 to 5 minutes.
Check ATS.
Check connections between ATS and controller.
Confirm whether the unit is in accordance with
the configuration of the remote sensing, remote
communication and remote control.
Check connections.
Check if COM port is correct.
Check if A and B of RS485 is connected
reversely
Check if PC COM port is damaged
is
not
Test voltage at generator terminals with a
multimeter.
Inspect all terminals of auxiliary board.
Inspect AVR push-on terminals.
Repair, or replace if necessary.
Restore magnetism of the exciter stator:
1、Operate the no-load generator at rated
speed.
residual
2、Attach the leads to a 12VDC battery with a
diode in one lead.
3、Briefly(maximum 1s) connect the positive
lead to the AVR terminal X+(F1) and
may
negative lead to AVR terminal XX-(F2).
Caution: The AVR will be damaged if it is
connected with wrong polarities and no diode.
33