nominal_current
Current setpoint sent to the vehicle when the device is operated in nominal charge mode.
By default it is the nominal current that shows on the charging station specification plate. Its value must be a
positive, whole number.
Its bottom limit is 6 Amps according to regulations and its top limit is the same as the current of the specification
plate.
For ZE Ready units, the bottom limit is 7 Amps for single-phase versions and 13 Amps for three-phase versions.
If compliance with these ranges is not met its previous value will be preserved.
Example:
nominal_current = 15;
limited_current
Current setpoint sent to the vehicle when the device is operated in limited charge mode.
By default it is 62.5% of the current on the specification plate of the charging station, 10 Amps for 20-Amp units
and 20 Amps for 32-Amp units.
Its value must be a positive, whole number. Its bottom limit is 6 Amps according to regulations and its top limit is
the same as the nominal_current.
For ZE Ready units, the bottom limit is 7 Amps for single-phase versions and 13 Amps for three-phase versions.
If compliance with these ranges is not met its previous value will be preserved.
Example:
limited_current = 12;
deferred_current
Deferred charging is possible in these charging stations thanks to configuration via USB.
Configure the current setpoint on this line to send to the vehicle when the device is operated in deferred charge
mode. By default it is the same as the nominal charge.
Its value must be a positive, whole number. Its bottom limit is 6 Amps according to regulations and its top limit is
the same as the current of the specification plate.
For ZE Ready units, the bottom limit is 7 Amps for single-phase versions and 13 Amps for three-phase versions.
If compliance with these ranges is not met its previous value will be preserved.
Example:
deferred_current = 16;
10
Power reference table as per phases, voltage and current
Single phase
230V 6 A
230V 8 A
230V 10 A
230V 12 A
230V 14 A
230V 16 A
230V 20 A
230V 24 A
230V 28 A
230V 32 A
1.38 kW
1.84 kW
2.30 kW
2.76 kW
3.22 kW
3.68 kW
4.60 kW
5.52 kW
6.44 kW
7.36 kW