Important installation notes
for cable glands of type CMP-...-A2F
User manual
Document No.
42/10-56 XU
Date of issue
07.05
Revision
02
Manufacturer
ABB Automation Products GmbH
Borsigstraße 2
63755 Alzenau
Germany
Tel:
+49 551 905-534
Telefax:
+49 551 905-555
CCC-support.deapr@de.abb.com
© Copyright 2005 by ABB Automation Products GmbH
We reserve the right to technical amendments
This document is protected by copyright. Information in this document is intended only to as-
sist the user in safe and efficient operation of the equipment. Its contents are not to be repro-
duced in full or part without prior approval of legal owner.
Important installation notes
General information
Type of cable gland
CMP-20/16-A2F
CMP-20s-A2F
CMP-20-A2F
Intended usage
– EEx d IIC and EEx e II (EN 50014, EN 50018 and EN 50019) for hazardous areas.
– Permanent operating temperature range -60 to +130 °C (with LSF sealing ring).
– Ingress protection type IP 66 / IP 67.
– Use only with permanently fixed enclosures of less then 2,000 cm³ volume.
– Use only with unarmored and permanently fixed cables with smooth elastomeric or plas-
tic sheath of suitable outside diameter.
Mounting instructions
1.
Verify used cable for suitability (type, operating temperature rating, outside diameter,
and so on).
2.
Prepare cable for mounting, check outside sheath for damages and soil.
3.
Insert cable into cable gland and tighten until the cable is firmly fixed and sealed by
the sealing ring.
4.
Clamp cable to prevent pulling and twisting.
4
Outside diameter of cable
3.5 to 8.7 mm
8.0 to 11.5 mm
11.0 to 13.5 mm
Important installation notes
EN
English
English
42/10-56 XU