Determination of the Residual Voltage VG for Various Connection
Types
The residual voltage can be calculated either from the three phase-to-ground voltages, or
it can be directly measured at the neutral terminal (e. g. of the generator) or over the
broken delta.
The method is selected (via setting parameter »VG[x] . Fuente VG«) for each instance of
the
residual voltage protection »VG[x]«
2.8.5.1
Calculation from the Three Phase-to-Ground Voltages
L1
L2
L3
V̲ L 12
V̲ L 23
V̲ L 31
The residual voltage is calculated from the three phase-to-ground voltages with the
following setting:
• »VG[x] . Fuente VG« = «calculado»
The residual voltage can be calculated only if the phase-to-ground voltages (star
connection) are connected to the measuring inputs of the device.
If the phase-to-phase voltages (delta connection) are measured instead of the phase-to-
ground voltages (star connection) it is not possible to calculate the residual voltage.
MCDGV4-3.7-ES-MAN