3.3
ACCESS TO INSTALLER'S
PARAMETERS
For access to the installer's parameters,
press simultaneously the keys
for 5 seconds (3 fig. 14).
For example, the parameter PAR 23 is
visualised on the display of the control
panel in the following way:
The paramet er s scr oll for war ds and
backwards with the key
and
the default parameters can be changed
with the keys
and
.
The standard visualisation returns automa-
tically after 60 seconds, or by pressing one
of the control keys (2 fig. 14).
3.3. 1
Replacing the board or
RESETTING parameters
If the electronic board is replaced or reset,
it is necessary to configure PAR 1 and PAR
2 by associating the following values to
each type of boiler to be able to restart the
boiler:
BOILER
GAS
MODELS
METHANE
20
25
30
BF/BFT
35
LPG
20
25
30
35
METHANE
25
OF/OFT
30
LPG
25
30
BOILER
OF/BF
OF/BF COMBINED
WITH SUN-PANEL SYSTEM
OFT - BFT - 25/55 - 30/55
SYSTEM
AQUAQUICK
NOTE: the inside of the upper door of the
boiler panel has a label with the values
that have to be set for PAR 1 and PAR 2
(fig. 21).
FAST CONFIGURATION
PAR DESCRIPTION
and
1
Combustion configuration
2
Hydraulic configuration
3
Timetable 2 programmer
4
Pressure transducer disabler
5
Assignment of auxiliary relay AUX
(D.H.W. tank)
6
Luminous bar indicating presence
of voltage
and
7
Allocation of CR 73 channels
8
--
9
--
10 Remote control option setting
11 Correction values external sensor
D.H.W. - HEATING
PAR DESCRIPTION
20
D.H.W. minimum temperature
21
D.H.W. maximum temperature
22
Anti-legionella (D.H.W. tank)
PAR 1
23
Boiler antifreeze
1
24
External sensor antifreeze
25
Climatic curve setting Zone 1
2
26
Climatic curve setting Zone 2
3
27
Minimum temperature Zone 1
4
28
Minimum temperature Zone 2
5
29
Minimum temperature Zone 2
6
30
Maximum temperature Zone 2
31
Maximum heating power
7
32
Post-circulation temperature
8
33
Pump activation delay Zone 1
9
34
Re-ignition delay
10
11
12
EXPANSION CHART
PAR DESCRIPTION
PAR 2
40
Assignment to mixed zones
1
41
Mix valve stroke time
2
42
Priority D.H.W. over mixed zone
43
Floor drying
3
4
5
RE-SET
PAR DESCRIPTION
49
Reset default parameters
(par. 01-par 02 = "-")
PARAMETERS INSTALLER
RANGE
UNIT OF
MEASUREMENT
-- = ND
1 ... 12
-- = ND
1 ... 5
1 = DHW + Recirc. pump
2 = DHW
3 = Recirculation pump
0 = Disabled
1 = Enabled
1 = Remote supply
2 = Recirculation pump
0 = Disabled
1 = Enabled
0 = Not assigned
1 = Circuit 1
2 = Circuits 1 and 2
--
--
1 = CR 73
2 = CR 53
3 = RVS
-5 ... +5
RANGE
UNIT OF
MEASUREMENT
10 °C ... PAR 21
PAR 20 ... PAR 62 OEM
0 = Disabled
1 = Enabled
- 5 ... +5
- 15 ... +5
3 ... 40
3 ... 40
PAR 64 OEM ... PAR 28
PAR 27 ... PAR 65 OEM
PAR 64 OEM ... PAR 30
PAR 29 ... PAR 65 OEM
30 ... 100
0 ... 199
0 ... 199
0 ... 10
RANGE
UNIT OF
MEASUREMENT
1 = Zone 1
2 = Zone 2
0 ... 199
0 = Paralle
1 = Absolute
0 = No activated
1 = Curve A
2 = Curve B
3 = Curve A+B
RANGE
UNIT OF
MEASUREMENT
-- , 1
INC/DEC
DEFAULT
UNIT
SETTING
=
=
"--"
=
=
"--"
=
=
1
=
=
1
=
=
1
=
=
1
=
=
1
--
--
--
--
--
--
=
=
1
°C
1
0
INC/DEC
DEFAULT
UNIT
SETTING
°C
1
30
°C
1
60
=
=
0
°C
1
3
°C
1
- 2
=
1
20
=
1
20
°C
1
20
°C
1
80
°C
1
20
°C
1
80
%
1
100
Sec.
10
30
10 sec.
1
1
Min.
1
3
INC/DEC
DEFAULT
UNIT
SETTING
=
=
1
10 sec.
1
12
=
=
1
=
=
0
INC/DEC
DEFAULT
UNIT
SETTING
=
=
=
ES
PT
GB
93