Descargar Imprimir esta página

Honeywell Home C7735A1000 Instrucciones De Instalación página 2

Publicidad

Idiomas disponibles

Idiomas disponibles

C7735A1000 DUCT AIR TEMPERATURE SENSOR
ZONE DAMPERS
BY PASS DAMPER
PLACE SENSOR
INTHIS AREA.
Fig. 2. DATS mounting location.
3. Drill a 1/4 in. hole in the duct at the location
selected for the sensor.
4. Attach wire using wire nuts and push them into
the cover, then insert the probe into the hole
drilled in step 2.
69-1521EFS—03
DO NOT
EVAPORATOR COIL
PLACE
SENSOR IN
THIS AREA.
HEAT EXCHANGER
BLOWER
M14877A
5. Secure the DATS to the side of the duct, through
the two mounting holes, with the screws sup-
plied.
IMPORTANT
Use 18-22 gauge thermostat wire for shorter
runs. For longer runs or when wiring near volt-
age, use shielded cable.
6. Run wire to zone panel or thermostat. See zone
panel or thermostat installation instructions.
2

Publicidad

loading

Este manual también es adecuado para:

C7735a1000/u