Clase 35 kv empalme para cables de energía dieléctricos extruidoscinta de cobre, pantalla de alambre,pantalla de plomo

Publicidad

Idiomas disponibles

Idiomas disponibles

If UniShield* Cable
*UniShield is a trademark of BICC General Cable Industries, Inc.
4. Remove insulation
Refer to Table 2 and cut back the insulation as shown.
5. Chamfer insulation; abrade insulation
Chamfer insulation for 1/4" (5mm) as shown.
Note: Chamfering is not required, but is recommended.
Abrade the insulation, as necessary to remove imbedded
semi-con, and clean.
6. Clean cable jacket(s)
Clean cable jacket(s) for the length of the nested tubes as shown.
7. Place nested tubes over cable
Protect tubes from end of conductor as they are placed over cable
ends.
8. Install connector
Note: Tyco Electronics recommends the use of connectors with
rounded or "tapered" ends, but they are not required.
After installation, deburr connector.
Using an approved solvent, clean the insulation as shown.
PII 53106
Revision AL
Choice 3
Z
"Z"
Insulation
X
Cutback
Y
Abrade
Insulation
1/4" (5mm) chamfer both cables
30"
Clean
(760mm)
*If using HVS-3523S, clean both jackets.
Insulation
Semi-Con
Metallic Shield
3
C L
A
C
"Y"
"X"
=
+
1/2 Length
Expansion
of Connector
Gap
Abrade
Insulation
30"
*Clean
(760mm)
Black/Red Triple Layer Tube
Red Insulating Tube
Black Stress Control Tube
Clean
Insulation
Connector
Semi-con
PCN 690615-000