DIP Switch Output Selection (HMD62)
You can change the humidity parameter that is output on the RH channel of HMD62 with the
DIP switches on the component board. Select the parameter you want the transmitter to
output by sliding the parameter's DIP switch to the right (ON). In the example in
(page
15), the transmitter's selected output parameter is dew point/frost point temperature
(T
). Keep the other DIP switches in the OFF position (left).
df
The selected parameter uses the default scaling shown in
Table 2 HMD62 Default Parameter Scaling
Parameter
RH
T
d
T
df
A
X
T
w
H
If you need to change the default scaling of a parameter, configure the output
with Vaisala Insight PC software. See the instructions in HMD60 User Guide.
CAUTION!
that the DIP switch selections override the Insight configuration. When using
Insight to configure the output, set all DIP switches to the OFF position (left) to
ensure they do not cause a conflict with the Insight settings.
Default Scaling for 4 ... 20 mA Output Range
0 ... 100 %RH
-40 ... +80 °C (-40 ... +176 °F)
-40 ... +80 °C (-40 ... +176 °F)
3
0 ... 300 g/m
(0 ... 131.1 gr/ft
0 ... 600 g/kg (0 ... 4200 gr/lb)
-40 ... +80 °C (-40 ... +176 °F)
-40 ... 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)
If you use the Insight software to further configure the output, note
Figure 10 HMD62 DIP Switch Example: T
Output Selected
RH
Relative humidity
Td
Dew point temperature
Tdf
Dew point/frost point temperature
A
Absolute humidity
X
Mixing ratio
Tw
Wet-bulb temperature
H
Enthalpy
Table 2 (page
15).
3
)
df
Figure 10
15