open Circuit Breaker
Insertion – Circuit Breakers ABW16...32
AttentIon!
Check if the removal carriage is fastened to the panel. If not, hold it so that
it does not fall over upon supporting the circuit breaker on the tracks.
I1) Pull the removal tracks on both sides outward to the maximum extent.
I2) Place the circuit breaker on the tracks, correctly positioning it on the existing projection.
I3) Push it inside the removal carriage until it reaches the end.
The circuit breaker will still be in the REMOVED (DISCONNECTED) position, with both the
power and control circuits disconnected.
I4) Press the off button to turn off the circuit breaker.