Arch extinguishing Chambers
Items
Dust and debris
Visual inspection.
General state of
Visual inspection.
chamber
Fastening of
Verification of
chamber
tightening torque.

operation Mechanism

Items
Charging of
Operation of
springs
manual charging.
Operation of
Turning on and
turning on and
off
off by the front
buttons.
protection unit
Items
External
Visual inspection.
appearance
Activation
Trip test.
Method of
Inspection
There must not be dust or
debris in the inside of the
chamber.
Chambers must be intact,
without cracks or damage.
Fastening bolts must be
tightened with a torque of
9~11 Nm.
Method of
Inspection
Verify if the springs can be
charged naturally.
The circuit breaker must
turn on and off normally.
Method of
Inspection
Unit must be intact,
without cracks or damage,
including selectors.
The unit must turn on and
off the circuit breaker.
Criteria
Criteria
Criteria
English
open Circuit Breaker
recommended
procedures
Remove dust and debris
with vacuum and dry cloth.
Replacement of chamber in
case of abnormalities.
Retighten with
recommended torque.
recommended
procedures
Replacement of the circuit
breaker in the ase of
abnormalities.
Replacement of the circuit
breaker in the case of
abnormalities.
recommended
procedures
Replacement of
protection unit in case of
abnormalities.
Replacement of circuit
breaker in case of
abnormalities.