Manual DV-12
• Plug the cord into the outlet of your 'clean'
group.
1.0 gENERAL
• Your DV-12 is now connected to the mains
voltage.
The DV-12 is a time controlled relay box with
which a maximum of 2 x 600 watt fittings or 2 x
1.4 CONNECTINg EqUIPMENT TO THE dv-12
400 watt fittings can be switched.
You can connect 2 x 600 watt or 2 x 400 watt fit-
1.1 TECHNICAL dATA
tings to your DV-12.
Dimensions
: 110 x 210 x 70mm.
In steps 1.2 and 1.3 you have;
Required voltage
: 230 Vac / 50Hz.
• Connected your DV-12 to a 'clean' group,
Max. Output
: 6 Amperes.
• Mounted it onto a flat surface,
Isolation level
: IP-44
• Connected it to the mains voltage.
1.2 REqUIREd (ACTIvE) vOLTAgE dv-12
Now the electrical ballasts (fittings) will have to
To connect the DV-12 you will preferably need a
be connected to the DV-12.
'clean' group of at least 6 Amp. A 'clean' group
Please read the installation manual carefully
means that this group will only be used by the by
before you connect the electrical ballasts, in
the DV-12. If you do not have a(n) (extra) 'clean'
order to connect them properly.
group we advise you to have the DV-12 installed
by a certified installer.
If the electrical ballasts have been properly
connected there will be a 230v. cord on each
The DV-12 has a 6 Amp thermal fuse.
of the electrical ballasts. Plug both cords of
the electrical ballasts into the power outlets
This fuse turns off the DV-12 automatically in
case of an overload and / or a short circuit..
(sockets) on the side of the DV-12. You now have
connected 2 electrical ballasts to the DV-12.
1.3 THE INsTALLATION Of THE dv-12
1.5 AdjUsTINg THE dv-12 fOR UsE
At the back of the DV-12 there are 2 mounting
brackets. This allows you to mount the DV-12
The DV-12 is now ready for use; we only have to
onto a (flat) surface.
adjust the time.
CAUTION!
• Remove the plastic cap of the time switch.
• On the right side of the clock you will find a
The analogue timer is a sensitive part of the DV-
12, and is not resistant to hard shocks.
3-position switch.
• Place the DV-12 close to your 'clean' group.
1
= Continue 'ON'
• At the bottom of the DV-12 you will find a
0
= Everything 'OFF'
grounded (230v.) connection cord
2 = The DV-12 switches at the set times.
• Install, if needed, a grounded outlet onto your
'clean' group.
10
Manual DV-12
• Put the 3-position switch on the clock 2
1.6 fOR YOUR sAfETY
• Now we have to determine when the DV-12
needs to be switched 'ON' and 'OFF'.
• The correct operation of the DV-12 is only
• Therefore, the pins (the so called 'running
guaranteed, if you observe this manual.
weights') that are around the clock need to be
pushed out.
• Although it is possible to install the DV-12
Are the pins pushed INWARDS; The clock will
yourself, we recommend to have this done by
switch 'OFF'.
a certified installer.
Are the pins pushed OUTWARDS; The clock
will switch 'ON'.
• Before installing the DV-12, the 220v. voltage
• To have the timer switch between 2 times (the
MUST be taken off the power point (Check
'ON' time, and the 'OFF' time), ALL the pins
this!)
between those 2 times need to be pushed out.
• The shortest switch position of the clock is 15
• This guide should only be used for the DV-12.
minutes.
• When you have determined the 'ON' and 'OFF'
• DAVIN
products are covered by a 1-year war-
®
times, turn the clock slowly (manually) clock-
ranty.
wise to make sure everything is correct.
• If you are sure that everything switches at the
• To qualify for this warranty, you are required
right time, the DV-12 is ready for use.
to return the DV-12 to the point of sale.
• If changes are made to DAVIN
without the express and written prior permis-
sion of the manufacturer, the warranty will
become void.
• The DAVIN
®
with improper installation of the DV-12.
• Neither the manufacturer, nor the importer,
nor the retailers of the DV-12 are liable for
damages arising from the use of the DV-12.