Engine Start Switch; Voltage Adjustment Rheostat; Warning Light - Wacker G50 Manual De Operación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

G50/G70/G85
c
On/I
Off/0
L1 L2 L3
CAUTION:
The convenience receptacles are not con-
nected through the main line circuit breaker but are
connected directly to the generator windings. As a result,
the receptacles are powered even with the main breaker
in the off "O" position. To turn off power to receptacles,
open the individual circuit breakers provided for each.
DANGER
DANGER OF ELECTROCUTION! High voltage is
present inside this panel when the generator is
operating!

1.17 Engine Start Switch

(e)
The engine start switch
"REMOTE START", off "O", and "RUN/START". The
"REMOTE START" position is the normal setting used
when using the generator as a back-up power supply
connected to a remote switch. In the REMOTE START
position the generator is in stand-by mode and will not
start until the remote switch closes. In the "RUN/START"
position the switch immediately initiates the engine start
cycle, pre-heats the engine, then activates the starter
motor to crank the engine.
When set in the "REMOTE START" or "RUN/START"
position this switch applies battery power to the engine
control module to turn on the LCD panel, and also
energizes the engine's electrical system. In the off "O"
position power to the engine's electrical system, includ-
ing the fuel solenoid, is disconnected.
All manuals and user guides at all-guides.com
20
15
12
8
INCHES
j
EMERGENCY STOP SWITCH
NOTAUSSCHALTER
INTERRUPTOR DE URGENCIA
INTERRUPTEUR D'URGENCE
TERMINAL DOOR OPEN
h
KLEMMENABDECKUNG OFFEN
PUERTA DE BORNES ABIERTA
CACHE-BORNES OUVERT
is a three-position switch:
Hz
Ø
A
V
STOP
g

1.18 Voltage Adjustment Rheostat

Directly below the engine start switch is the voltage
(f)
adjustment rheostat
. Use the rheostat to adjust the AC
voltage output. Turn adjusting screw clockwise to in-
crease voltage, counter-clockwise to decrease voltage.
The voltage can be monitored at the LCD panel.

1.19 Warning Light

(d)
The amber warning light
turn on prior to an engine fault condition occurring. This
acts as a pre-alarm to call attention to a potential fault
condition. At the same time the warning light goes on, the
LCD panel will begin blinking to indicate which engine
function is approaching its fault value.
Engine Pre-alarm Set Points:
• Fuel Level = 25%
• High Temperature = 234° F
• Low Temperature = 70° F
• Low Oil Pressure = 20 psi
• Time to Service = 0 hours
• Sender Failure = engine coolant and oil pressure
senders.
Note: Time to Service and Sender Failure faults will not
shut down the generator.
OPERATION
1A
d
e
REMOTE START
FERNSTART
ARRANQUE REMOTO
DEMARRAGE A
DISTANCE
START/RUN
START/LAUF
ARRANQUE/MARCHA
DEMARRAGE/MARCHE
1026SD72
f
on the metering panel will
1A-19

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido