G50/G70/G85
1.22 Convenience Receptacles
The generator is equipped with three 120V/240V twist
(e)
lock receptacles
rated at 50A. The two 120V duplex
(f)
receptacles
are equipped with ground fault interrupts
(GFI). Receptacles do not connect through the main line
circuit breaker. Each receptacle is protected by its own
(c, d)
circuit breaker
which is located directly above it.
Power to the receptacles is available any time the gen-
erator engine is running, even with the main line circuit
breaker open.
Note: When the voltage selector switch is in the 480/277 V
3Ø position, voltage at the duplex receptacles is 139 V,
and voltage at the 50 A receptacles is 139/240 V. When
the voltage selector switch is in the 208/120 V 3Ø
position, voltage at the 50 A receptacles 120/208 V.
All manuals and user guides at all-guides.com
1.23 Remote Run Terminal Block
The remote run terminal block
of the 120V duplex receptacles. It provides connection
points for installation of a remote start switch. When it is
connected to a transfer switch, it allows the generator to
be used as a standby power supply.
1.24 Panel Door Interlock Switch
The customer connection lugs panel access door is
equipped with an interlock switch
opened this switch automatically trips the main circuit
breaker and disconnects power to the generator voltage
regulator. Voltage to the receptacles will not be cut.