4.1.5 Group F, level control
Code
Description
22
HIGH
High level probe / float / minimum pressure switch input
23
LOW
Low level probe input
24
COM
Probes / float / minimum pressure switch common circuit
Characteristics:
Voltage 3.6Vp-p
4.1.6 Group G, analog inputs/outputs
Code
Description
25
GND_A
Sensor cable screen connection electronic ref.
26
Out_A
Analog signal output
27
AI1
Sensor 1 active value input
28
AI2
Sensor 2 active value input
29
PWR_A
Sensor power supply +13.5 Vdc
Characteristics:
Voltage 0-11 V, accuracy 0.3%;
Current input 0-22 mA, accuracy 0.3%, protection against short circuit.
Maximum input voltages = 30 Vdc.
4.1.7 Group H, Power supply
Code
Description
30
PE
Earth connection
31
0Vac
Board power supply
32
24Vac
Board power supply
Characteristics:
Voltage 24Vac +/-10%
Frequency 50/60Hz
4.2 View of bypass jumpers
The bypass jumpers bypass the electronics, directly activating the pump control contactors without
any regulating control.
They are used in an emergency, when the electronic board is out of use and it is necessary to ensure
pump operation.
OPEN position = The pump contactors are deactivated.
CLOSE position = The pump contactors are permanently activated and no regulating control is
carried out (to be used only in emergency situations).
SOFTWARE position = pump contactors controlled by the electronic board.
The default position of the jumpers is SOFTWARE.