Installation Instructions
Installation on Mounting Bracket
Ø 2 ,5 m m
1
2
Installation of Actuators
Following the installation of the Actuators onto the
heating circuit valves (see actuator installation instruc-
tions) the Actuator must be connected to the Basis
Wireless as follows.
Plug/clamp connections
The following wire types are suitable for the plug/
clamp connections:
solid wire: 0.5 - 1.5 mm²
flexible wire: 1.0 - 1.5 mm²
For a proper connection, 10 mm of the line ends
should be stripped.
The Actuator wire's factory-mounted end sleeves pro-
vide a proper connection without stripping.
<3 mm
17
AB 4071-6 / AB 4071-12
Push the actuator cables
into the clamp.
For flexible wires, open
the clamp with a screw-
driver and plug the cable
in.
A maximum of 4 actua-
tors per heating zone
can be connected to the
6 room base, and 2 actua-
tors per heating zone can
be connected to the 12
room base.
A maximum of 13 Actuators may be connect-
ed to the Basis Wireless. 4 (2) actuators may
be connected per channel. However, several heating
zones can be allocated to a Wireless Thermostat.