Connecting the hob
For the various connection options, use the brass terminal bridges located in the casing.
Single-phase connection 230V~1P+N:
Place a terminal bridge between terminals L1 and L2, then between terminals L2 and L3 and then
between terminals N1 and N2.
Connect the earthing to the « earth » terminal, the neutral to terminal N1 or N2, and phase L to
terminal L1 or L2 or L3.
Two-phase connection 400V~2P+N:
Place a terminal bridge between terminals L1 and L2, then between terminals N1 and N2.
Connect the earthing to the « earth » terminal, the neutral to terminal N1 or N2, phase L1 to
terminal L1 or L2 and phase L2 to terminal L3.
Three-phase connection 400V~3P+N:
Place a terminal bridge between terminal N1 and N2.
Connect the earthing to the « earth » terminal, the neutral to terminal N1 or N2, phase L1 to
terminal L1, phase L2 to terminal L2 and phase L3 to terminal L3.
Model 2 heating zones: 5IZ34291
Mains
230V~50/60Hz
( * ) as per standard EN 60 335-2-6
Caution! Insert the wires correctly and tighten the screws.
We are not responsible for incidents resulting from incorrect connections or non-existent or
inadequate ground connections.
Connection
1 phase + N
Diameter
3 x 1.5 mm²
31
Cable
Fuse
H 05 VV - F
16 A *
H 05 RR - F