Electrical Connections
Process D: Steps 1 through 4, At The House, continued
STEP
4B
Correct 230 Volt and 115 Volt Connections
(Grn)
System
Ground
Main
Circuit
Breaker
Typical 230 Volt Connection via a Double Pole Breaker
(which contacts both bus bars). Ground (green wire)
connects to neutral bar.
Two Common and Dangerous 230 Volt Installation Errors
Do not use two single pole (i.e. 5 Volt) circuit breakers to run your 230 Volt pump.
Here's Why:
A: With the breakers connected to adjacent terminals, one breaker
connects to each bus bar. If one breaker trips, that wire will have no
voltage on it and the motor will stop.
However, the other wire and the motor will still have voltage and
can shock you if you touch them.
(Grn)
A
Main Circuit
Breaker
23833A09
Warning! Hazardous voltage and risk of dangerous or fatal electrical shock.
Be sure power is disconnected before installing or servicing your pump.
230 Volt
(Blk)
230V
Incoming Power
115V
(Blk)
115V
Neutral Bar
Ground
(Green)
(Blk)
Power
to Pump
(Blk)
Double
Pole
Circuit
Breaker
Bus Bars
5701 0907
Incoming Power
(Blk)
(Blk)
Ground
(Green)
2 Single Pole
Breakers
Bus Bars
5703 0907
(Grn)
System
Ground
Main
Circuit
Breaker
Bus Bars
Typical 115 Volt Connection via a Single Pole Breaker (which
contacts one bus bar). Ground (green wire) and White (neutral wire)
both connect to the neutral bar.
Black wire is the hot side and white wire is the neutral side of the
5 volt circuit.
B: With the breakers connected with one space between them, they
contact the same bus bar. With no voltage differential between the
lines, the motor won't run.
A voltage check from either breaker to the neutral bar or wire will
show 5 volts – correct but misleading.
A voltage check from one breaker to the other will show 0 (zero)
volts - dangerous and misleading, because although there is no
voltage between breakers, each breaker is still connected to its own
live 5 volt circuit.
(Grn)
B
Main Circuit
Breaker

115 Volt
(Blk)
230V
Incoming Power
115V
(Blk)
115V
Neutral Bar
Ground
(Green)
Neutral
(Wh)
from Pump
Power
(Blk)
to Pump
Single
Pole
Circuit
Breaker
5702 0907
Incoming Power
(Blk)
(Blk)
Ground
(Green)
(Blk)
2 Single Pole
Breakers
Bus Bars
Bag #23834A004
5704 0907