Valid until Display
GPRS
activated
GPRS
activated
GPRS
activated
GPRS
activated
30
Description
GPRS settings
Interval for the cyclical transmission of the data to
the server.
Station number of the switchgear on the server
Activation of the transmission of the GPRS data
The menu with the sensor settings
The measurement range of the (relative) pressure
sensor for the final pressure of the pressure-boost -
ing system. Can only be changed when the drives
are switched off.
If the intention is to use absolute pressure sensors,
please contact Wilo customer service.
The electrical signal type of the pressure sensor.
Can only be changed when the drives are
switched off.
Attention!
The corresponding jumper setting must be selected
on the printed circuit board for a voltage signal
(0/2 – 10 V)!
Reaction in the event of a sensor fault (stop or a
pump runs at a specified speed). Can only be
changed when the drives are switched off.
Parameter range
Factory setting
0 ... 3600
0 ... 9999
ON
OFF
0 – 6
0 – 10
0 – 16
0 – 25
0 – 40
0 – 10 V
2 – 10 V
0 – 20 mA
4 – 20 mA
Stop
Var