Ribind AC07068 Manual Del Usuario página 22

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

G
B
remote control has been correctly programmed, the DL2 LED (green) will flash once.
4 - The code programming time resets automatically so that you can programme the next
remote control.
5 - To finish programming, let 10 s pass and then press the PROG. button briefly. The red DL1
LED will stop flashing.
6 - Turn DIP 1 to OFF and DIP 3 to OFF.
IF THE DL1 LED CONTINUES TO FLASH RAPIDLY, THIS MEANS THAT DIP 1 IS STILL POSITIONED TO
ON AND ANY MANOEUVRE HAS BEEN DELETED.
PROCEDURE FOR DELETING ALL RADIO CODES USED ONLY FOR COMPLETE OPENING
You can only delete the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 s.
3 - Press and hold the PROG button for 5 s. The green DL2 LED will flash twice to confirm that
the stored codes have been deleted.
4 - The red programming DL1 LED remains active and you can programme new codes as shown
above if required.
5 - Turn DIP 1 to OFF and DIP 3 to OFF.
HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR COMPLETE OPENING
You can only check the memory if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored).
3 - After this, the DL1 programming LED will remain active for 10 s, so that you can delete all
codes if required.
4 - Turn DIP 1 to OFF and DIP 3 to OFF.
FUNCTIONING OF CONTROL ACCESSORIES
ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors) used on
the installation are set in the IMPULSIVE mode, otherwise, the gate will be operated even
without the protection of the safety devices.
STEP BY STEP or AUTOMATIC commands
(K BUTT button, PED BUTT button, RADIO REMOTE button)
DIP 6 - ON The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform the cyclic
command open-stop-close-open-stop-etc.
DIP 6 - OFF The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as
described in Point D.
CLOCK FUNCTION
If you want the Clock Function must request K with firmware 12 NOUP.
A CLOCK CONNECTED TO K with fw 05 or more ACTIVATES THE AUTOMATIC MOVEMENT
OF THE GATE WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES!
The Clock Function is useful during rush hours, when traffic is heavy and the flow is slow (e.g.
entrance/exit of employees, emergencies in residential areas or car parks and, temporarily, for
removal vans) and it's necessary to keep the gate opened.
CLOCK FUNCTION APPLICATION
It is necessary to request a K control panel with firmware 12 NOUP.
Select the automatic functioning DIP 6 OFF.
It can be done by connecting a switch and/or a daily/weekly clock either in parallel to the K
BUTT button or instead of the K BUTT button. When the control board receives this command,
the gate will open and by keeping this contact closed for all the time of the gate opening, the
Clock Function is automatically activated. In fact, once reached the open position, the gate will
remain opened and all of the control board functions are blocked. Only when K BUTT contact is
released, the control board functions are re-activated and the Automatic Closing restarts (if
enabled) doing the countdown to the gate closing.
PEDESTRIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for example, to permit a
pedestrian crossing. In fact, the Pedestrian command (see Point E) is carried out only by
opening the gate just enough for a pedestrian to pass, as described into the Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or disabled with
DIP 3.
From the Pedestrian opening position, the gate can be completely opened by the OPEN or by the
K BUTT button or by the RADIO button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning DIP 3 to ON.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be enabled turning DIP 3 to ON.
The maximum gap of time that can be programmed is 5 minutes (see Point E).
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM) - Safety function - PL "b" according to EN13849-1
DIP 4 OFF => the photocells are active both in gate opening and in gate closing. In this
configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the obstacle is
removed
- while the gate is still, it will not move neither in opening nor in closing.
DIP 4 ON => the photocells are active only in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still if a close
command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell receivers must
be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump
(from PHOT to COM) to permit the gate to operate.
In case the receiver led remains lit, malfunctioning of the
main supply is suspected.
It is advisable to connect electrically to earth the columns
or the photocells stands to the terminal A -, to shield the
photocells from external noise.
Be careful not to short circuit the system when the supply
phases are inverted!
SAFETY STRIP (EDGE - COM) - Safety function - PL "b" according to EN13849-1
If it intervenes during opening, it inverts the movement and closes for 2 s and then stops.
If it intervenes during closing, it inverts the movement and opens for 2 s and then stops.
If the safety strip remains engaged (NO contact), no automatic movement is allowed.
In case the safety strip is not installed, this contact must be short circuited with a wire jump
(from EDGE to COM) to permit the gate to operate.
it is highly recommended to check safety-strips operation at least every 6 months.
SAFETY STRIP ALARM
After the inversion given by the intervention of the safety edge, the gate stops in alarm mode
and this is signaled by the blinker on for 1 minute and by the buzzer on for 5 minutes.
During or after the minute of alarm, the normal gate operations can be restored by pressing
any push button.
TESTING THE SAFETY STRIP equipment
DIP 10 ON => enables to test the safety strip equipment.
The test is performed every time the gate completes a full opening. The test is available only if
the safety strip device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the A+TEST and
A- outputs (DIP 10 ON). Automatically, every time the gate completes a full opening, just before
closing, the control board switches OFF the A+TEST and A- power supply output for a very short
time. While the safety strip power supply is switched OFF, if everything is working fine the
safety strip contact (EDGE - COM) must open. In case the test fails, no other gate manoeuvre
will be allowed and the alarm state will be signalled by both the Blinker and the Buzzer, if
installed, which will remain on for 5 minutes
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP 10 MUST BE LEFT OFF.
STOP BUTTON - Safety function - PL "b" according to EN13849-1
If the Automatic command is enabled (DIP 6 OFF), a Normally Closed contact could be
connected in series to the COM wire of the opened and the closed limit switches.
This contact works like a STOP button to interrupt any gate manouver.
22
24 Vdc
Term.
A -

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ba03227Abk0006Abk0007K-crx 230vK-crx 120v

Tabla de contenido