7. MOST FREQUENT PROBLEMS
Motor doesnt start
The motor starts and stops
The generator doesnt
produce electricity
High or low voltage vacuum
Voltage lower than
nominal voltage
Unstable voltage
The generator stops
Machine is out of fuel
Dead or low battery
Fuel filter blocked
Air or water in the fuel line
Valve recession
Ducts blocked
A safety device is on
Cable improperly connected
or bad connection
Air filter blocked
Slow idle
Fuel filter blocked
Air in the fuel line
Tank vent blocked
Defective base supply
The circuit breaker is unplugged
Excitation problem
Engine speed too slow
Problem with the alternator
Alternator not adjusted properly
Engines RPMs too low
Too much charge
Engines RPMs too low
Unreliable contacts
Stopped as a safety measure
Air intake
C/ Oilamendi, 8 - 10
C/ Oilamendi, 8 - 10
01015 VITORIA - SPAIN
01015 VITORIA - SPAIN
Tel.: (34) 945 29 22 97
Tel.: (34) 945 29 22 97
FAX: (34) 945 29 22 98
FAX: (34) 945 29 22 98
ayerbe@ayerbe.net
ayerbe@ayerbe.net
www.ayerbe.net
www.ayerbe.net
Add fuel
Replace or charge
Check and change
Purge
Take apart and polish valve seats
Take apart and clean
Check and resolve the safety
device problem
Review the diagram and modify
Replace
Change it to 51.5 Hz
Replace
Purge
Clean
Check and change if necessary
Plug in the circuit breaker
Check with a Service Technician
Check the engine speed
Check
Adjust the voltage on
the regulation board
Adjust the RPMs
Check and reduce the charge
Adjust the RPMs
Check the connections
Check the alarms and resolve
the problem
Check and eliminate